scholarly journals A Novel Control Strategy for Grid-Connected Inverter Based on Iterative Calculation of Structural Parameters

Energies ◽  
2018 ◽  
Vol 11 (12) ◽  
pp. 3306 ◽  
Author(s):  
Zhenao Sun ◽  
Dazhi Wang ◽  
Tianqing Yuan ◽  
Zairan Liu ◽  
Jiahui Yu

A novel control strategy that is based on iterative calculation of structural parameters is proposed for grid-connected inverter in this paper. The proposed strategy has a good dynamic performance, which makes it particularly suitable for the application of PV grid-connected generation. First, a second-order discretization mathematical model of grid-connected inverter control is established in the dq frame. The corresponding relation between the control signal and the output current is deduced in formulas. Then, the values of structural parameters in the formulas can be obtained through iterative calculation, which can further reduce the amount of calculation. After several iteration cycles, the structural parameters are approximately equal to their actual values and the inverter can be controlled as an open-loop system with its dynamic performance optimized. At last, simulation and experiments are performed. The results show that the static performance of the proposed strategy is as good as that of the classical ones, but its dynamic performance is improved significantly.

2021 ◽  
Vol 2136 (1) ◽  
pp. 012015
Author(s):  
Shengqing Li ◽  
Xinluo Li ◽  
Qiang Wu ◽  
Xiafei Long

Abstract In order to further optimize the output current harmonic suppression effect of photovoltaic grid-connected inverters, a composite control strategy of LCL type photovoltaic grid-connected inverter output current is proposed. This strategy combines proportional complex integral (PCI) control and repetitive control (RC) in parallel, draws a composite control block diagram, introduces a transfer function, and designs PCI and RC control parameters. Prove that the compound control can reduce current harmonics, achieved the purpose of reducing the steady-state error of the fundamental frequency. And adopts a new PCI composite control strategy, which helps to save the cost of the control system. By building the MATLAB/Simulink simulation platform and establishing the PCI+RC composite control model of LCL photovoltaic grid-connected inverter, the comparison of the simulation results shows that compared with the PI+RC control strategy, the total harmonic distortion rate of the grid-connected current is reduced by 25.77. %, significantly improving the quality of grid-connected current.


2012 ◽  
Vol 241-244 ◽  
pp. 636-640
Author(s):  
Wu Wu Tang ◽  
Liang Liang Chen ◽  
Hong Xu Yin ◽  
Hao Dong

This paper developed a mathematical model of three-phase PV grid-connected inverter, and studied the grid-connected current control method based on PI control in synchronous rotating reference frame. Simulation and experimental results from the prototype of 30kW three-phase PV grid-connected inverter proved the correctness and the feasibility of the control strategy, and this grid-connected inverter can operate at the unity power factor state with a nice dynamic performance, and the output current has high sinusoidal and low harmonic content as well as good symmetry.


2013 ◽  
Vol 291-294 ◽  
pp. 2464-2469
Author(s):  
Dian Li Hou ◽  
Qing Fan Zhang ◽  
Xiao Liu

Because of the powerful filtering ability the third-order LCL filters has been widely used in grid-connected inverters, but there are some problems to be solved on systems stability and control accuracy. A separated-PID control strategy has been proposed according to the PID characteristics and the structural features of a single-phase inverter connected to the grid with a LCL filter. This control strategy has some advantages as a strong dynamic tacking stability, and the system output has a small steady state error. A detailed description is presented on this control strategy applied in the single-phase grid inverter with a LCL filter. According to the Routh-Hurwitz stability criterion, the stability of a grid-connected inverter system based on the proposed control strategy has been analyzed. Finally, waveforms of this inverter have been presented through a simulation to show the steady and dynamic performance of the proposed scheme.


Author(s):  
Yiyan Zhang ◽  
Xiaobo Tang ◽  
Zhongyu Shen ◽  
Xiao Chen ◽  
Yulong Feng ◽  
...  

2013 ◽  
Vol 415 ◽  
pp. 81-88
Author(s):  
Yang Xue ◽  
Yuan Li ◽  
Jia Dong Zhang ◽  
Jing Lin ◽  
Jun Tao Yang

The space vector pulse width modulation (SVPWM), as a new kind of vector control technique, has the advantages of high voltage utilization, less distorted output, simple control method, etc. In this paper, the control technique is applied to three-phase photovoltaic (PV) grid-connected inverter system. It uses double loop control method combined with PI control technique. The simulation model of PV grid-connected inverter system is established in Matlab/Simulink. The simulation results show that the application of SVPWM technique effectively improves the dynamic performance of PV grid inverter system and the THD of grid-connected current is low.


2013 ◽  
Vol 303-306 ◽  
pp. 1145-1148
Author(s):  
Jia Guo ◽  
Zhi Gang Li ◽  
Ya Ping Cheng ◽  
Kai Huang ◽  
Chun Yan Cui

The grid-connected inverter plays an important role in the photovoltaic power generation systems, the output of the grid current harmonics affect the stability of the grid. The reason of grid inverter output current distortion, a detailed analysis of current waveform control strategy and its effectiveness of the grid-connected inverter harmonic current suppression is introduced based on the d-q coordinates in this paper.


2013 ◽  
Vol 846-847 ◽  
pp. 543-546
Author(s):  
Yue Zhou

A kind of Cuk grid-connected inverter is proposed for renewable energy power generation. The grid-connected inverter using Cuk input series output parallel circuit, form a new type of non isolated single stage output parallel input series double Cuk inverter circuit. Firstly, On the basis of the topological structure and principle, the double-loop control strategy is researched to enhance its adaptability and robustness. Simulative results show that,the proposed inverter with double-loop control has better dynamic and static performances, with less output current harmonics and better waveform quality.