Review for "Development of an adaptive differential protection scheme for transformer during current transformer saturation and over‐fluxing condition"

Energies ◽  
2021 ◽  
Vol 14 (7) ◽  
pp. 1857
Author(s):  
Jingde Xia ◽  
Shaozhuo Li ◽  
Shuping Gao ◽  
Wenquan Shao ◽  
Guobing Song ◽  
...  

In view of the difficulties in coordination between reliability and sensitivity of conventional generator differential protection, this paper presents a novel generator differential protection scheme based on a new braking method. On the basis of the mathematical model of the field-circuit coupling method and the electrical network cascade characteristics, the stator windings were combined and decoupled by the improved six-sequence component method to eliminate electromagnetic coupling between winding coils. In accordance with the basic characteristics of longitudinal impedance, the function of sub-item discrimination was realized. Numerous simulations and the up-to-date dynamic experiments showed that the proposed method has good state discrimination ability and can effectively resist the influence of current transformer saturation. Thus, it has an excellent prospect for engineering promotion.


Sign in / Sign up

Export Citation Format

Share Document