The conventional distance protection scheme malfunctions sometimes in case of a fixed series capacitor compensated transmission line due to the change in relaying impedance of the protected line during faulty conditions. In order to mitigate this problem, a combined discrete Fourier transform and fuzzy (CDFTF) based algorithm has been proposed in this paper. This method has been tested on a 400 km, 735 kV series compensated transmission line network and WSCC 3-machine 9-bus system for all fault types using MATLAB/Simulink and PSCAD platforms, respectively. A fixed series capacitor is located at the middle of the protected line. The fundamental components of phase currents, phase voltages, and zero-sequence current are fed as inputs to the proposed scheme. The fault detection, faulty phase selection, and fault classification are achieved within 1/2–1 cycle of power frequency. The proposed CDFTF-based scheme is less complex and is better than other data mining techniques which require huge training and testing time. Test results corroborate the proposed scheme reliability with wide variations in fault location, fault resistance, fault inception angle, evolving faults, compensation level, and heavy load interconnection. The results discussed in this work indicate that the proposed technique is resilient to wide variations in fault and system conditions.