scholarly journals Experimental research on the indoor temperature and humidity fields in radiant ceiling air-conditioning system under natural ventilation

Author(s):  
Tao Huang ◽  
Yutong Xiang ◽  
Yonghong Wang
Author(s):  
Tobias Heidrich ◽  
Jonathan Grobe ◽  
Henning Meschede ◽  
Jens Hesselbach

The following paper describes an economical, multiple model predictive control (EMMPC) for an air conditioning system of a confectionery manufacturer in Germany. The application consists of a packaging hall for chocolate bars, in which a new local conveyor belt air conditioning system is used and thus the temperature and humidity limits in the hall can be significantly extended. The EMMPC calculates the optimum energy or cost humidity and temperature set points in the hall. For this purpose, time-discrete state space models and an economic objective function with which it is possible to react to flexible electricity prices in a cost-optimised manner are created. A possible future electricity price model for Germany with a flexible EEG levy was used as a flexible electricity price. The flexibility potential is determined by variable temperature and humidity limits in the hall, which are oriented towards the comfort field for easily working persons, and the building mass. The building mass of the created room model is used as a thermal energy store. Considering electricity price and weather forecasts as well as internal, production plan-dependent load forecasts, the model predictive controller directly controls the heating and cooling register and the humidifier of the air conditioning system.


2011 ◽  
Vol 280 ◽  
pp. 71-75
Author(s):  
Zhong Chao Zhao ◽  
Dong Hui Zhang ◽  
Yu Ping Chen

In this paper, the operation mechanism of combined air-conditioning system with temperature and humidity decoupled treatment (CACSTHDT) was presented, and the energy saving potential and economics of CACSTHDT were primarily analyzed through compared with a traditional air-conditioning system. The results indicated that CACSTHDT could save up to 28.64% energy consumption in comparison with a traditional air-conditioning system. The operating cost in one summer only was 71.36% of that cost of traditional air-conditioning system.


2019 ◽  
Vol 111 ◽  
pp. 01085
Author(s):  
Hiroshi Muramatsu ◽  
Tatsuo Nobe

In this study, an office building in Japan that incorporates energy-saving features and environmental technologies was investigated. This office building features a green façade, natural ventilation, a concrete slab with no suspended ceilings, and thermo-active building systems. Two airconditioning systems were installed in this building—a ceiling radiation air-conditioning system and a whole floor-blow off air conditioning system. In addition, a natural ventilation system was installed. We surveyed the heat flux of the ceiling surface and indoor thermal environment of this building from 2015 through 2016. The ceiling using the heat storage amount of concrete maintains a constant temperature in the workplace during as well as after office hours. We also performed detailed measurements of the heat flux of the ceiling surface and indoor thermal environment in the summer of 2017. The results showed that the ceiling radiation air-conditioning system provided a stable thermal environment. Furthermore, we report that making use of the thermal behavior of the skeleton improved the operation of the ceiling radiation airconditioning system.