Single-phase Grounding Fault Location Method for Distribution Network Based on Convolutional Neural Network

Author(s):  
Jiefeng Liang
2014 ◽  
Vol 494-495 ◽  
pp. 1739-1742
Author(s):  
Hong Yu Yang

In China,most of distribution system is neutral noneffectively grounded. And the single-phase fault often happens through cement pole. In this paper,firstly,the voltage of the fault phase and the current of cement pole are derived in 10kV neutral noneffectively grounded distribution systems when cement pole has single-phase ground fault.Secondly,the online fault location method is proposed based on voltage gradient of cement pole.Thirdly,the resistence characristic of cement pole is analyzed and the distance obtained from the gradient voltage of cement pole is given.Finally, the theoretical analysis and simulation experiments show that the method is feasible.


2015 ◽  
Vol 713-715 ◽  
pp. 1369-1372
Author(s):  
Xue Ming Zhai ◽  
Huan Xia ◽  
Long An

Based on the analysis of the transient process of the electric line’s developing ground fault, this paper applies the oppositely-directed travelling wave fault location method to fault location in distribution network. Simultaneously, this paper chooses proper wavelet generating functions to find the modulus maximum of oppositely-directed travelling waves and summarizes the methods and steps of this oppositely-directed travelling wave fault location. Finally, PSCAD/EMTDC is used to simulate the single-phase ground fault to verify the oppositely-directed travelling wave fault location method.