Research on a Distance Relay-Based Wide-Area Backup Protection Algorithm for Transmission Lines

2017 ◽  
Vol 32 (1) ◽  
pp. 97-105 ◽  
Author(s):  
Mengxiao Chen ◽  
Huifang Wang ◽  
Shaofei Shen ◽  
Benteng He
Author(s):  
B. Mallikarjuna ◽  
P. V. Vardhan Varma ◽  
S. D. Samir ◽  
M. Jaya Bharata Reddy ◽  
D. K. Mohanta

2014 ◽  
Vol 2014 ◽  
pp. 1-12
Author(s):  
Zhe Zhang ◽  
Xiangping Kong ◽  
Xianggen Yin ◽  
Zengli Yang ◽  
Lijun Wang

In order to solve the problems of the existing wide-area backup protection (WABP) algorithms, the paper proposes a novel WABP algorithm based on the distribution characteristics of fault component current and improved Dempster/Shafer (D-S) evidence theory. When a fault occurs, slave substations transmit to master station the amplitudes of fault component currents of transmission lines which are the closest to fault element. Then master substation identifies suspicious faulty lines according to the distribution characteristics of fault component current. After that, the master substation will identify the actual faulty line with improved D-S evidence theory based on the action states of traditional protections and direction components of these suspicious faulty lines. The simulation examples based on IEEE 10-generator-39-bus system show that the proposed WABP algorithm has an excellent performance. The algorithm has low requirement of sampling synchronization, small wide-area communication flow, and high fault tolerance.


Sign in / Sign up

Export Citation Format

Share Document