Pressure Drop Analysis of Steam Condensation in a Plate Heat Exchanger

1999 ◽  
Vol 20 (1) ◽  
pp. 71-77 ◽  
Author(s):  
L. K. Wang, B. Sunden, Q. S. Yang
2010 ◽  
Vol 27 (4) ◽  
pp. 563-571 ◽  
Author(s):  
R. A. F. Cabral ◽  
J. A. W. Gut ◽  
V. R. N. Telis ◽  
J. Telis-Romero

1968 ◽  
Vol 32 (11) ◽  
pp. 1127-1132,a1 ◽  
Author(s):  
Katsuto Okada ◽  
Minobu Ono ◽  
Toshio Tomimum ◽  
Hirotaka Konno ◽  
Shigemori Ohtani

1999 ◽  
Vol 121 (1) ◽  
pp. 110-117 ◽  
Author(s):  
A. Muley ◽  
R. M. Manglik

Experimental heat transfer and isothermal pressure drop data for single-phase water flows in a plate heat exchanger (PHE) with chevron plates are presented. In a single-pass U-type counterflow PHE, three different chevron plate arrangements are considered: two symmetric plate arrangements with β = 30 deg/30 deg and 60 deg/60 deg, and one mixed-plate arrangement with β = 30 deg/60 deg. For water (2 < Pr < 6) flow rates in the 600 < Re < 104 regime, data for Nu and f are presented. The results show significant effects of both the chevron angle β and surface area enlargement factor φ. As β increases, and compared to a flat-plate pack, up to two to five times higher Nu are obtained; the concomitant f, however, are 13 to 44 times higher. Increasing φ also has a similar, though smaller effect. Based on experimental data for Re a 7000 and 30 deg ≤ β ≤ 60 deg, predictive correlations of the form Nu = C1,(β) D1(φ) Rep1(β)Pr1/3(μ/μw)0.14 and f = C2(β) D2(φ) Rep2(β) are devised. Finally, at constant pumping power, and depending upon Re, β, and φ, the heat transfer is found to be enhanced by up to 2.8 times that in an equivalent flat-plate channel.


Sign in / Sign up

Export Citation Format

Share Document