Adaptive Distance Relay Based on Estimation And Update of Two-Port Equivalent Across Transmission Lines

Author(s):  
Vedanta Pradhan ◽  
O. D. Naidu ◽  
Neethu George
2014 ◽  
Vol 1044-1045 ◽  
pp. 482-485
Author(s):  
Jin Hu Zhang ◽  
Zhen Yu Xu ◽  
Zhi Peng Su

The distance relays of transmission lines find limitations in the presence of series compensated capacitor. One of them is the distance relay setting issue, in which either over-reach problem or under-reach problem may occur. To deal with this issue, a differential equation based adaptive distance relaying setting method for series compensated line is proposed. As for it do not need to identify whether SC/MOV is in fault loop, not need to know the parameters and the operating states of SC/MOV/GAP, and furthermore, it can be realized without the iterative calculation, it is very suitable to be used for the distance relaying adaptive setting of series compensated line. Simple simulation results certificate the proposed adaptive setting method.


2017 ◽  
Vol 32 (1) ◽  
pp. 97-105 ◽  
Author(s):  
Mengxiao Chen ◽  
Huifang Wang ◽  
Shaofei Shen ◽  
Benteng He

Author(s):  
Minghao Wen ◽  
Deshu Chen ◽  
Xianggen Yin