An experimental study on the fire extinguishing characteristics of water mist and compressed air foam in a railway tunnel rescue station

Author(s):  
Kai Yao ◽  
Wanfu Liu ◽  
Weiping Han ◽  
Jianjun Xia ◽  
Ya Liu ◽  
...  
2013 ◽  
Vol 790 ◽  
pp. 53-56
Author(s):  
Chen Jian ◽  
Xu Yan Ying ◽  
Wang Na

This paper presents an experimental study of fire suppression effectiveness with water mist containing FeCl2 additives.The investigation focuses on suppression effectiveness under various FeCl2 additives concentrations,working pressures and nozzle different height above the fire source . The experimental results show that: there is a significant impact on fire suppression effectiveness when adding FeCl2 to water mist. There is an optimum additive concentration of extinguishing fire, corresponding to the shortest extinguishing time, the least amount of water, the highest efficiency of extinguishing fire. The nozzle working pressures and nozzle position have effect on the performance of the water mist extinguishing: the greater the pressure is, the shorter water mist fire extinguishing time is. Under the same experimental conditions, the closer the water mist nozzles are to the oil pan, the shorter extinguishing time is.


2012 ◽  
Vol 30 (2) ◽  
pp. 138-157 ◽  
Author(s):  
Na Meng ◽  
Longhua Hu ◽  
Shuai Liu ◽  
Long Wu ◽  
Longfei Chen ◽  
...  

2004 ◽  
Vol 12 (3) ◽  
pp. 209-222