The mechanism of fault searching for new energy distribution network based on variation of cutting current

Author(s):  
Yingke Zhao ◽  
Zhiqian Bo ◽  
Qingping Wang ◽  
Xiaowei Ma ◽  
Neng Jin ◽  
...  
2019 ◽  
Vol 13 (1) ◽  
pp. 17-23
Author(s):  
Helbert Eduardo Espitia Cuchango ◽  
Iván Machón González ◽  
Hilario López García ◽  
Domingo Guzmán Díaz González

Energy distribution systems present alterations in the voltage profile in their nodes when distributed generation elements are installed. As a consequence, tension can be risen in a level beyond the admissible. This paper presents the optimization to three fuzzy controllers located in a distribution network with radial topology. The optimization of each controller is performed using the maximum descent algorithm, which is separately carried out; thus, having a distributed approach. The interaction between generators is considered to perform this process; the results show that the adjustment of the controllers is achieved


2014 ◽  
Vol 960-961 ◽  
pp. 1376-1380
Author(s):  
Chong Xin Xu ◽  
Yan Jun Jiao

Power generation becomes a main way of using new energy. However, the access of distributed generation(DG) causes the ordinary protection system develop a series of problems. In this paper, the structure of distribution network with DG is introduced firstly.Secondly,it is analysed that the effect that DG brings to distribution network protection, and then a new protection scheme of distribution network with DG is put forward. The segment I, II of direction three-current protection on the line which is at the upstream of DG, and the next line’s segment I, II consists of a simple communication unit. Through the comprehensive judgment of two protections’ action results, fault can be isolated in minimum range quickly and accurately. Finally, the correctness and feasibility of the new protection principle are verified by simulating a 10KV distribution system.


Sign in / Sign up

Export Citation Format

Share Document