When the single phase ground fault occurs in resonant grounded system, there are significant differences in the components of fault phase current between fault line and non-fault line. This feature can be reflected by intrinsic mode entropy (IMEn) of fault current. IMEn is a new signal analysis over multiple oscillation levels. It corresponds to the sample entropy (SampEn) and the empirical mode decomposition (EMD). The results of fault simulations in different conditions indicate that the method is reliable.