Static aspects of nonlinear voltage dependent load sensitivities in steady state voltage stability analysis

Author(s):  
S.R. Fernandes
2017 ◽  
Vol 09 (04) ◽  
pp. 317-327 ◽  
Author(s):  
Shuo Yang ◽  
Weisheng Wang ◽  
Chun Liu ◽  
Yuehui Huang ◽  
Chi Li ◽  
...  

Author(s):  
GABER EL-SAADY ◽  
MOHAMED A. A. WAHAB ◽  
MOHAMED M. HAMADA ◽  
M. F. BASHEER

The influence of series Flexible AC Transmission Systems (FACTS) device namely, Thyristor-Controlled Series Capacitors (TCSC) on the steady state voltage stability is the main objective of this paper. The Line stability Index LSI under excepted lines outage contingencies is used to identify the critical line which is considered as the best location for TCSC. A modal analysis is used to define the weakest bus of the studied system. The FACTS device is implemented and included into the Newton-Raphson power flow algorithm, and the control function is formulated to achieve the voltage stability enhancement goal. The analysis is preformed on standard IEEE 30 bus system. The proposed scheme are tested under different loading conditions and different nonlinear voltage dependent loads. The simulation results demonstrate the feasibility and effectiveness of the device and the proposed algorithm.


Author(s):  
Ronnapa Paosateanpun ◽  
Songsak Chusanapiputt ◽  
Sukumvit Phoomvuthisarn ◽  
Sotdhipong Phichaisawat

Sign in / Sign up

Export Citation Format

Share Document