The evolution in semiconducting devices has introduced flexible control on a system but it has also penetrated harmonics in the grid, which results in extra electrical stress and load. Limiting the presence of harmonics in the grid and low power factor maintained by consumers has become of utmost priority to the power system analyst. Hence, the need for Active Filter emerges. Here, a real-time simulation, in dSPACE- Targetlink, of shunt harmonics active filter is propounded. The possible basic control strategy used in the simulation is ”Instantaneous Power Theory”. Control logic of two features of Active Filter viz., Global Harmonics Elimination, and Reactive Power Compensation are produced in the paper. The results obtained in ”Software In Loop Mode” of dSPACE are discussed and verified in detail. The richness of the code generated by the dSPACE- Target link can be reasoned by observing the results which are well aligned with the industrial standards regarding the harmonics.