scholarly journals A STUDY ON AIR-CONDITIONING LOAD CALCULATION METHOD CONSIDERING THERMAL SENSATION OF RESIDENTS

2012 ◽  
Vol 77 (682) ◽  
pp. 957-966
Author(s):  
Jun CUI ◽  
Toshiyuki WATANABE
2021 ◽  
pp. 014459872110052
Author(s):  
Yuechao Liu ◽  
Dong Guo ◽  
Min Zhou ◽  
Shanshan Wu ◽  
Dongmei Li

One optimization method of hourly heat load calculation model for heat storage air-conditioning heating system in different climate zones was proposed. A building model is initially built in six different climate zones. Subsequently, the hourly heat load and steady-state design heat load in different climate zones were analyzed. Simultaneously, the hourly heat load additional coefficient of the air-conditioning system with different heating modes on a typical day was compared. It can be found that steady-state design heat load on a typical day is mostly between the peak load and average load of the air-conditioning heating system. Simultaneously, results indicate that the hourly heat load additional coefficient in each climate zone can be fitted to different exponential functions. When the heat storage capacity of building components was changed, the maximum increase of the hourly heat load additional coefficient of the air-conditioning system with intermittent heating was 5%. Thus, the research of the optimal design of hourly heat load calculation method provides a relative reference for performance improvement of the heat storage air-conditioning heating system.


Sign in / Sign up

Export Citation Format

Share Document