Analysis of the Impact of Distributed Generation on Distribution Network Protection

2012 ◽  
Vol 433-440 ◽  
pp. 5924-5929 ◽  
Author(s):  
Jie Dong ◽  
Ya Jun Rong ◽  
Chun Jiang Zhang

With the connection of distributed generation (DG), structure of traditional distribution network changes and original relay protection scheme should be adjusted. On the basis of introducing the concept and advantages of distributed generation, this paper discusses the influence of distributed generation with different position or different capacity on current protection. The paper analyzes magnitude and distribution of fault current under short-circuit condition and change curves of fault current are given, which provides some theoretical basis for new relay protection scheme.

2014 ◽  
Vol 960-961 ◽  
pp. 1376-1380
Author(s):  
Chong Xin Xu ◽  
Yan Jun Jiao

Power generation becomes a main way of using new energy. However, the access of distributed generation(DG) causes the ordinary protection system develop a series of problems. In this paper, the structure of distribution network with DG is introduced firstly.Secondly,it is analysed that the effect that DG brings to distribution network protection, and then a new protection scheme of distribution network with DG is put forward. The segment I, II of direction three-current protection on the line which is at the upstream of DG, and the next line’s segment I, II consists of a simple communication unit. Through the comprehensive judgment of two protections’ action results, fault can be isolated in minimum range quickly and accurately. Finally, the correctness and feasibility of the new protection principle are verified by simulating a 10KV distribution system.


2018 ◽  
Vol 3 (10) ◽  
pp. 38-44
Author(s):  
D. C. Idoniboyeobu ◽  
S. L. Braide ◽  
Wigwe Elsie Chioma

This research work proposed an improved Resonant Fault Current Limiting (RFCL) protection scheme to reduce the impact of three-phase short-circuit faults in a power system sub-transmission network. The model used an interpolator-extrapolator technique based on a Resonant Fault Current Limiter (RFCL) for automating the procedure of predicting the required reactor value that must be in resonant circuit to limit the short-circuit current values to permissible values. Using the developed model, short-circuit fault simulations on the three phases of the transmission line (Phase A-C) were performed in the MATLAB-SIMULINK environment. Simulation results were obtained by varying the resonant inductance (reactor) parameter of the RFCL circuit for each of the phases to obtain permissible short-circuit current levels and the values used to program a functional interpolator-extrapolator in MATLAB; the resonant values were typically set to values of inductance equal to 0.001H, 0.01H and from 0.1H to 0.5H in steps of 0.1H. Simulation results revealed the presence of very high short-circuit current levels at low values of the resonant inductor. From the results of simulations, there are indications that the RFCL approach is indeed very vital in the reduction of the short circuit current values during the fault and can safeguard the circuit breaker mechanism in the examined power system sub-transmission system. In addition, lower fault clearing times can be obtained at higher values of inductances; however, the clearance times start to converge at inductance values of 0.1H and above.


2021 ◽  
Author(s):  
Haymanot Takele Mekonnen

Abstract BackgroundOne of the new technologies in generating power near the distribution system is called distributed generation which has supportive and destructive characteristics to the power system protection. One of the destructive characteristics of distributed generation is increasing the level of fault current to the protective equipment of the power system. In addition to increment of fault, it also alters the radial nature of the power distribution system and cause the power bidirectional rather than unidirectional. Integration of distributed generation to the distribution network causes increment of fault current effect, reliability drop, and affects security of protection system. The level of failure of protection be contingent on type, size, location and number of distributed generation. This fault current can cause a great damage to the electrical equipment with the miss operations of protective devices. The main aim of this paper is analysis of the fault current level to the protection of distribution network due to the integration of distributed generation which concerns on solar distributed generation, wind distributed generation and combination of solar and wind distributed generations at a time. This paper conducts the analysis for the increment of fault current by the integration of distributed generation and its impact on distribution network protection. ResultsThe analysis and the modeling are conducted on the 15KV distribution network of the radial feeder in Debre Markos town. This paper has covered the ling to ground, line to line and three phase fault analysis and their impact on the protection of distribution system for the wind and solar distributed generation types. After the integration of the distributed generation the fault current is increased by 0.529KA for three phase, 0.74KA for line to ground, 0.467KA for line to line and 0.523KA for line to line to ground. ConclusionsThis paper confirms designing distribution network without forecasting the future demand of electric power users give the protection equipment additional requirement. As the result, the fault current after the integration of distributed generation to the distribution network have great value in terms of power system protection.


2017 ◽  
Vol 41 (6) ◽  
pp. 383-396 ◽  
Author(s):  
Naser El Naily ◽  
Saad M Saad ◽  
Zakariya Rajab ◽  
Faisal Mohamed

Although integration of wind distributed generation directly into the distribution level has considerable advantages, increased penetration of wind distributed generation (renewable distributed generation) alters the network configuration and jeopardizes the protection system operation and system stability; for this reason, necessary changes in power system protection philosophy must be achieved. Modern numerical relays offer extraordinary features and fast and accurate methods for spotting and detecting different unbalanced operating conditions and can be used to mitigate the influence of integrating wind distributed generation into distribution network. In this study, an adaptive directional negative protective scheme was implemented in the medium-level distribution network to investigate and evaluate the performance of protection system and introduce new adaptive protective scheme based on negative overcurrent protection to increase the selectivity and sensitivity of the protection system in case of unbalanced faulty conditions. The medium-level distribution network of Libya Eastern electric network had been implemented in ETAP software to address and evaluate the efficiency of the proposed approach.


2014 ◽  
Vol 1070-1072 ◽  
pp. 923-928
Author(s):  
Peng Sun ◽  
Ming Wu Luo ◽  
Zhao Xia Sun ◽  
Tian Ci Liu ◽  
Chang Hong Deng ◽  
...  

In light of the rapid development of the electric power grid, the integrated application of distributed generation (DG) units can be considered as a key driver. Nevertheless, along with large number of DG units are connected into a distribution network, maybe different kinds of effects are accordingly induced. In particular, regarding the configured relay protection, its selectivity and sensitivity may be affected. In this paper, the penetration capacity analysis of DG considering overcurrent relay protection and flux-coupling type FCL is conducted. Under different fault conditions, the theoretical impacts of introducing DG on the fault current are investigated, and a flux-coupling type FCL is suggested to limit the fault current and potentially enhance the DG’s access capacity. Furthermore, the detailed simulation model of a typical distribution network integrated with the DG and FCL is created. From the simulation results, the employment of the FCL can effectively reduce the fault current’s negative influence on the DG, and improve the DG’s access capacity to a certain extent.


2012 ◽  
Vol 433-440 ◽  
pp. 1950-1956
Author(s):  
Xiao Ming Li ◽  
Sha Li ◽  
Peng Lu ◽  
Shu Qiong Liu

When distributed generation (DG) accesses to non-system bus , and the power capacity increases to a certain extent, it will cause malfunction of protective devices, as a result of which ,protective devices lose selectivity. This paper analyzes influence to relay protection of power system as a result of the access of DG, establishes a model of the access of DG, and proposes principles of reconfiguration of protection devices, and re-setting of relay protection when DG accesses to power system. This method provides a theoretical basis for designing of DG accessing to power system, reconfiguration of protection devices and re-setting of relay protection.