Transmission Line Backup Protection Based on Negative Sequence Current Differential Algorithm Using IEC-61850 Asynchronous Data from an Adjacent Substation

Author(s):  
Sun-Woo Lee ◽  
Nam-Ho Lee ◽  
Soon-Ryul Nam
2021 ◽  
Vol 11 (6) ◽  
pp. 2608
Author(s):  
Chien-Hsun Liu ◽  
Willybrordus H. P. Muda ◽  
Cheng-Chien Kuo

A power transformer (PT) in power generation or transmission is critical to maintaining electrical continuity. Fault detection on a PT is needed, especially of incipient faults, which are often caused by a turn-to-turn fault (TTF) before it develops into a more severe fault. We use a hybrid algorithm between conventional and modern techniques to detect a developing fault in a PT. The current response signals from a negative sequence current directional algorithm, extended park vector algorithm (EPVA), differential negative sequence current, and EPVA-fuzzy system are combined to distinguish the possibility of a TTF. The subalgorithms are combined using a hybrid detection algorithm to distinguish the faults. The model is a 10 MVA, three-phase PT with Δ-Y configuration 150/300 kV, simulated using MATLAB Simulink software. The results show that by combining the subalgorithms, several limitations are distinguished within the TTF with a slight increase in accuracy.


IEEE Access ◽  
2020 ◽  
Vol 8 ◽  
pp. 135329-135338
Author(s):  
Zhenxing Li ◽  
Zhihao Xie ◽  
Zhenyu Wang ◽  
Hanli Weng ◽  
Lu Wang