Experimental investigation of heat transfer and pressure drop characteristics of internal finned tubes

Author(s):  
Yu-Wen Pai ◽  
Rong-Hua Yeh
Author(s):  
Ignacio Carvajal-Mariscal ◽  
Florencio Sanchez-Silva ◽  
Georgiy Polupan

In this work the heat transfer and pressure drop experimental results obtained in a two step finned tube bank with conical fins are presented. The tube bank had an equilateral triangle array composed of nine finned tubes with conical fins inclined 45 degrees in respect with the tube axis. The heat exchange external area of a single tube is approximately 0.07 m2. All necessary thermal parameters, inlet/outlet temperatures, mass flows, for the heat balance in the tube bank were determined for different air velocities, Re = 3400–18400, and one constant thermal charge provided by a hot water flow with a temperature of 80 °C. As a result, the correlations for the heat transfer and pressure drop calculation were obtained. The experimental results were compared against the analytical results for a tube bank with annular fins with the same heat exchange area. It was found that the proposed tube bank using finned tubes with conical fins shows an increment of heat transfer up to 58%.