Research for Forming up the Controlling Diagram Utilizing the Connection of a LV Resistor on Voltage Transformer’s Open-Triagle Coil to Reduce over Voltage Caused by Earth Fault in 6 kV Grid of QuangNinh Underground Mines
Keyword(s):
Single phase earth-fault in MV grids usually causes overvoltage that harm to human being and electric equipment. If the magnitude of over voltage is so great, many grids’ eco-technical parameters will be affected. The paper analyzes all possible consequences of over voltage occurred in 6 kV grid of QuangNinh underground mines. Base on the analysis, a controlling diagram utilizing the connection of a LV resistor on voltage transformer’s open-triangle coil to reduce over voltage is recommended. The simulation results of the diagram are used to prove the effectiveness of solution: the over voltage magnitude is only in the range of (2,1–2,4).Uf. Other advantage that solution brings to relay system will be pointed out.