Investigation of turbine generator rotor winding inter-turn short circuit fault based on harmonic detection

Author(s):  
Wu Yucai ◽  
Li Yonggang ◽  
Wan Shuting ◽  
Li Heming
2011 ◽  
Vol 143-144 ◽  
pp. 125-131 ◽  
Author(s):  
Yong Gang Li ◽  
Guo Wei Zhou ◽  
Yu Ca Wu ◽  
He Ming Li

This paper analyzes the calculation method of unbalanced electromagnetic force by rotor winding inter-turn short-circuit fault, analytical calculating method neglects saturation, cogging and other factors, so the calculation accuracy is not high, in order to accurately calculate the magnetic field and the unbalanced electromagnetic force, this paper propose to analyze generator magnetic field by a finite element software Ansys, the obtained magnetic field data are further used to analyze the distributed electromagnetic force and the total force that generator rotor suffered, electromagnetic force distribution law of different slots, different levels of inter-turn short-circuit are got, which provide a basis for further studying the full force on generator rotor.


2013 ◽  
Vol 427-429 ◽  
pp. 230-234
Author(s):  
Wen Jing Zhang ◽  
Yong Gang Li ◽  
Yu Ca Wu

Inter turn short circuit fault is very common for turbine-generator, which will produce unbalanced electromagnetic force (UEMF) together with its relevant fault, namely dynamic eccentric, on the rotor. After complete finite element simulation by ANSYS, The relationship of rotor winding short positions and short degrees with UEMF were studied. And then, only the dynamic eccentric fault occurs, the relations of dynamic eccentric angles and dynamic eccentric degrees with UEMF were discussed as well. Whats more, by comprehensive consideration of the two faults, the characteristic of the force and its change law were researched. This paper provides a viable path to study the vibration law and fault diagnosis of turbine-generator in multi-source stress.


2014 ◽  
Vol 1033-1034 ◽  
pp. 1343-1349
Author(s):  
Yong Gang Li ◽  
Jie Jia ◽  
Liu Wan

Hydro-generator unit is the most important energy conversion device in the hydropower, which is directly related to the safety and reliability and stable operation of the hydroelectric power plant. When the turbine generator rotor winding inter-turn short circuit occurs, the proposed method using load curve electromagnetic characteristics analysis, the use of before and after the failure to find the relative change in the excitation current failure rate as the identification method, the criterion may reflect the severity of the failure, perform theoretical calculations, and thus the inter-turbine generator rotor windings short circuit simulation, consistent with the conclusions of the theoretical analysis.