Estimation of electrical power system steady-state stability in load flow calculations

1975 ◽  
Vol 94 (3) ◽  
pp. 1034-1041 ◽  
Author(s):  
V.A. Venikov ◽  
V.A. Stroev ◽  
V.I. Idelchick ◽  
V.I. Tarasov
2021 ◽  
Vol 10 (2) ◽  
pp. 550-558
Author(s):  
Rudy Gianto ◽  
Kho Hie Khwee

Modeling of wind power plant (WPP) is a crucial issue in power system studies. In this paper, a new model of WPP for steady state (i.e. load flow) studies is proposed. Similar to the previous T-circuit based models, it is also developed based on equivalent T-circuit of the WPP induction generator. However, unlike in the previous models, the mathematical formulation of the new model is shorter and less complicated. Moreover, the derivation of the model in the present work is also much simpler. Only minimal mathematical operations are required in the process. Furthermore, the rotor voltage value of the WPP induction generator is readily available as an output of the proposed new model. This rotor voltage value can be used as a basis to calculate the induction generator slip. Validity of the new method is tested on a representative 9-bus electrical power system installed with WPP. Comparative studies between the proposed method (new model) and other method (previous model) are also presented


Author(s):  
Fredy Estuardo Tamayo Guzmán ◽  
Carlos Andrés Barrera-Singaña

Electrical power systems are exposed to several events that can cause unstable operation scenarios. This is due to improper operation of certain components. If an event occurs, the system must be designed to overcome that contingency, thus remaining in a permanent condition that must be evaluated in order to monitor and prevent a possible collapse of the system. An evaluation of steady state stability is proposed at this work based on the capacity curves of generators, transformers and transmission lines. These remarked curves provide information on the operation point of these elements, thus allowing the application of remedial actions. PowerFactory and Matlab are used to carry out the tool for monitoring the operation points after a contingency. The effectiveness of the developed tool is validated at the IEEE 39-bus power system model, where results shows that the functionalaty for different contingencies based on the operating conditions when the components of the power system are varied, cosnquently, the tool identifies cases that require actions at the operational level.


2016 ◽  
Vol 41 (29) ◽  
pp. 12603-12617 ◽  
Author(s):  
Labed imen ◽  
Labed Djamel ◽  
Mansour Zohra ◽  
Fetissi Selwa

Author(s):  
M. E. Yusoff ◽  
H. Hashim

Power System Protection is very important in electrical power system as it minimizes power supply interruption to customers, and also prevents damages to electrical equipment.  Lately, renewable energy (RE) penetration in power system helps to support and fulfil the increasing demand of electricity to customers. However, the contribution of power from RE such as solar photovoltaic (PV) will increase the fault level and lead to reverse power flow; thus, it will affect power system protection reliability. This paper focuses on evaluating the reliability of differential protection relay during steady state, internal and external faults conditions when the power system is without and with solar PV penetration. Steady state and three-phase symmetrical line fault will be simulated in IEEE 39 bus test system using Power System Simulation for Engineering (PSS<sup>®</sup>E) software.


Author(s):  
Zulfiqar Ali Shahani

Electrical power system without interruption is the need of every consumer. Therefore, supplying electrical power which must be efficient, reliable and secure from any disturbance is the priority of power supply companies. But, due to changes in weather conditions and continuous load variations, small disturbances arise which may lead to severe disturbance. All electrical generating stations are interconnected, so a failure in any one unit can affect other generating units, therefore analysis is compulsory to solve the problem in the least time, and avoid a further big loss. Analysis of steady-state stability or transient stability plays a key role in a power system which helps to understand the behavior of a dynamic system. The stability problem is concerned with the behavior of the generating station when the system puts on either small or large disturbance. In this work, the steady-state stability (SSS) analysis of the Jamshoro thermal power plant (JTPP) is analyzed by using the eigenvalue method and linearization technique at four different reheat gain values. We develop a nonlinear mathematical model of JTPP and discuss its linearized form, and examine the behavior of the system stability using eigenvalues. The eigenvalue method analyzes the behavior of synchronous machine when system load varies continually. Numerical values of eigenvalues consist of either real part or real as well as imaginary parts. These eigenvalues help to understand the stability of the system, as to whether the system is stable or not.