Periodic Tests Improvement of Emergency Diesel Generator Units in Nuclear Power Plant

Author(s):  
Liu Fei

Abstract Domestic diesel-generator units of M310 reactor nuclear power plants at present adopt the French standard RCC-E 2005 emergency for periodic tests. During low-power periodic tests, the diesel-generators are not adequately protected, and there is a risk of serious damage to equipment. This article analyzes in detail the provisions of the IEEE 387 standard for the periodic tests of emergency diesel-generator unit, improves the periodic tests of the emergency diesel-generator unit according to the IEEE 387 standard, cancels the original low-power tests, and uses the test during the normal operation of the unit in order to solve this problem. The grid-connected test method and detailed analysis of the improved test content make the EDG periodic test method more economical and safe. The improvement has been approved by the nuclear safety regulatory agency, which provides an important reference for the related periodic test improvement of nuclear power plants.

ANRI ◽  
2020 ◽  
pp. 31-44
Author(s):  
Aleksey Ekidin ◽  
Aleksey Vasil'ev ◽  
Maksim Vasyanovich ◽  
Evgeniy Nazarov ◽  
Mariya Pyshkina ◽  
...  

The article presents the results of field studies in the area of the Belarusian NPP in the pre-operational period. The «background» contents of gamma-emitting radionuclides in individual components of the environment are determined. The main array of dose rate measurements in the area of the NPP construction site is in the range 0.048 ÷ 0.089 μSv/h. External radiation in the surveyed area is formed at 96% due to 40K, 226Ra and 232Th. The information obtained can be used to correctly interpret the data of future radiation monitoring during normal operation of nuclear power plants.


2019 ◽  
Vol 61 (3) ◽  
pp. 352-364 ◽  
Author(s):  
A. A. Ekidin ◽  
K. L. Antonov ◽  
M. E. Vasyanovich ◽  
I. A. Kapustin ◽  
I. Yu. Filatov

2013 ◽  
Vol 336-338 ◽  
pp. 313-318
Author(s):  
Chang Jian Deng ◽  
Hong Yang Hu ◽  
Jian Zhong Ling

To do Validation and Verification" of wireless vibration sensor nodes in NPPs (nuclear power plants), embedded system software test should be done. The test index is analyzed firstly; then the method of 'Temb' was introduced to analysis ADXL202 vibration nodes; the characteristic of system was used to establish LITO(life cycle, Infrastructure, Techniques, Organization) matrix, they are of emphasizing safety, application in harsh environment, using algorithms of technology and science and so on. The acceleration circulation method using fixed time cycle pretest by instrument and other weak was proved to be infeasible though FMEA (failure modes and effects analysis). Then FTA (fault tree analysis) is used to analyze system, so the software filter and real-time cycle test method were used to improve test precise and reliability of node vibration measurement. Experiments have proved its effective.


Sign in / Sign up

Export Citation Format

Share Document