scholarly journals IRP Control Based LSCPWM-Multilevel DSTATCOM for Power Quality Improvement

Majority of the consumer loads are of non-linear in nature and bring about deprived quality of power in distribution system. FACTS based DSTATCOM is a compensating device placed in shunt to power line to improve the power quality eliminating the effect of harmonics in source components. The paper presents multi-level DSTATCOM in distribution system to enrich the quality of power. Five-level cascaded H-Bridge structures DSTATCOM is employed to drive with compensating signals for power quality improvement. Five-level DSTATCOM is triggered from multi-carrier LSCPWM pattern. Reference signals are generated from IRP based control theory. The proposed system is capable to compensate for system unbalance, power factor and harmonics in the system. Simulation work of the proposed concept is carried out and the results are presented using MATLAB/SIMULINK software.

2020 ◽  
Vol 8 (6) ◽  
pp. 1462-1465

D-STATCOM has been used to improve the power quality problems, such as voltage sags, voltage swells for different fault conditions. In order to improve the power factor and reduce the harmonic distortions, LCL passive filter is used along with D-STATCOM. The aim of this paper is to compensate the voltage sag and harmonic distortions by designing the D-STATCOM with LCL passive filter across the distribution system. The simulations were performed by using MATLAB/SIMULINK.


Author(s):  
Faheem Ali ◽  
Muhammad Naeem Arbab ◽  
Gulzar Ahmed ◽  
Majid Ashraf ◽  
Muhammad Sarim

Pakistan is faced with energy crises from the last two decades. Generation cannot balance the load demands of the electricity consumers. Power delivery systems are generally old-fashioned and overloaded. They are unable to provide consistent and uninterrupted supply to commercial, industrial, and domestic loads. Generally speaking, the Power Systems consist of loads that are inductive and resistive in nature. Heavy machinery, induction motors, and arc furnaces are heavily inductive in nature. Inductive loads when operated in a weak power system results in lagging VARs (Volt Ampere Reactive) and poor voltage regulation, which must be balanced by the same number of leading VARs in order to ensure unity power factor and thus helps in improving the voltage profile. At times the reactive VARs injected may not be sufficient to balance the VARs requires by the system, but still the power factor is improved up to some extent. In hot and humid climatic conditions, air-cooling system and chillers greatly burdens the grids. Such loads require excessive reactive VARs, and if not offered with ample reactive power, causes severe voltage drops in distribution system. To manage low voltages and power-factor, household users use automatic voltage regulators while industries connect capacitor banks. Voltage regulators control output voltage within the required limits at the expense of excessive line current from transformer, which may overburden it. Moreover, with each operation of tap changer, current rises which further intensifies line losses. Static capacitors provide stable voltage but repeated variations in load demands reliable and vigorous voltage regulation. This investigation aims to come up with a power quality improvement scheme which would deliver instantaneous control of power (reactive) with SVC (Static VAR Compensator) thus overcoming the shortcomings of step-wise banks of capacitors and or voltage regulators. Simulation work is carried out in MATLAB/SIMULINK and the results are compliance with IEEE Standards for SVCs. The device can offer steady state as well as dynamic VAR compensation under changing load conditions. Result showed considerable improvement both in terms of response time and power factor. Switching time has been improved to less than 1/10th fraction of a second which in previous simulations was 0.7 seconds approximately. Initial power factor without disturbance and without compensation was recorded to be 0.6 lagging, which after compensation was improved to 0.95 lagging. Similarly, in presence of disturbance without compensation the power factor fluctuated between 0.55 and 0.9 lagging, which after compensation was improved to 0.95 lagging and above throughout the course of operation.


To improve the power quality of multi-feeder distribution system, this paper proposes a concept of Interline Power Flow Controller (IUPQC). IUPQC is a structure of two filters such as, series and shunt filters. The causes for poor power quality of system is due to harmonics, power factor variations and changes in system voltage. The purpose of these converters is to mitigate the PQ issues. The reference signals required for series and shunt converters of iUPQC system is generated with the help of conventional controllers and PWM controllers. The PLL used to match the phase sequence of converters. For obtaining better improvement in Power Quality this paper is implemented with one of the optimization technique such as Bull Optimization Technique (BOA). The purpose of BOA is used to control the DC Link Voltage of iUPQC. With the help of this BOA technique, the variations in voltage and current are reduced to enhance the power quality. The effectiveness of this proposed system with BOA technique is tested and verified using Matlab/ Simulink environment


Author(s):  
Faheem Ali ◽  
Muhammad Naeem Arbab ◽  
Gulzar Ahmed ◽  
Majid Ashraf ◽  
Muhammad Sarim

Pakistan is faced with energy crises from the last two decades. Generation cannot balance the load demands of the electricity consumers. Power delivery systems are generally old-fashioned and overloaded. They are unable to provide consistent and uninterrupted supply to commercial, industrial, and domestic loads. Generally speaking, the Power Systems consist of loads that are inductive and resistive in nature. Heavy machinery, induction motors, and arc furnaces are heavily inductive in nature. Inductive loads when operated in a weak power system results in lagging VARs (Volt Ampere Reactive) and poor voltage regulation, which must be balanced by the same number of leading VARs in order to ensure unity power factor and thus helps in improving the voltage profile. At times the reactive VARs injected may not be sufficient to balance the VARs requires by the system, but still the power factor is improved up to some extent. In hot and humid climatic conditions, air-cooling system and chillers greatly burdens the grids. Such loads require excessive reactive VARs, and if not offered with ample reactive power, causes severe voltage drops in distribution system. To manage low voltages and power-factor, household users use automatic voltage regulators while industries connect capacitor banks. Voltage regulators control output voltage within the required limits at the expense of excessive line current from transformer, which may overburden it. Moreover, with each operation of tap changer, current rises which further intensifies line losses. Static capacitors provide stable voltage but repeated variations in load demands reliable and vigorous voltage regulation. This investigation aims to come up with a power quality improvement scheme which would deliver instantaneous control of power (reactive) with SVC (Static VAR Compensator) thus overcoming the shortcomings of step-wise banks of capacitors and or voltage regulators. Simulation work is carried out in MATLAB/SIMULINK and the results are compliance with IEEE Standards for SVCs. The device can offer steady state as well as dynamic VAR compensation under changing load conditions. Result showed considerable improvement both in terms of response time and power factor. Switching time has been improved to less than 1/10th fraction of a second which in previous simulations was 0.7 seconds approximately. Initial power factor without disturbance and without compensation was recorded to be 0.6 lagging, which after compensation was improved to 0.95 lagging. Similarly, in presence of disturbance without compensation the power factor fluctuated between 0.55 and 0.9 lagging, which after compensation was improved to 0.95 lagging and above throughout the course of operation.


Energies ◽  
2018 ◽  
Vol 11 (11) ◽  
pp. 2927 ◽  
Author(s):  
Desmon Petrus Simatupang ◽  
Jaeho Choi

This paper proposes a multi-functional Photovoltaic (PV) inverter based on the Unified Power Quality Conditioner (UPQC) configuration. Power quality improvement is a difficult issue to solve for isolated areas or islands connected to the mainland through long submarine cables. In the proposed system, the line voltage is compensated for by the series inverter while the shunt inverter delivers the PV generating power to the grid. Depending on the technical conditions of power quality and system environment, it has five different operating modes. Especially during poor power quality conditions, the sensitive load is separated from the normal load to provide a different power quality level by using the microgrid conception. In this paper, the control method and the power flow for each mode are described, and the operational performance is verified through a PSiM simulation so that it can be applied to the power quality improvement of weak grid power systems such as in isolated areas or on islands connected to the mainland by long submarine cables.