Comparison of Impedance Based and Travelling Waves Based Fault Location Methods for Power Distribution Systems Tested in a Real 205-Nodes Distribution feeder

2018 ◽  
Vol 19 (2) ◽  
pp. 123-133 ◽  
Author(s):  
Mona Hosseinikia ◽  
Vahid Talavat
Author(s):  
Wen Fan ◽  
Yuan Liao ◽  
Ning kang

AbstractAccurate fault location in distribution systems greatly shortens maintenance time and improves reliability. This paper presents novel methods to pinpoint fault location and identify possible bad measurements for enhanced accuracy. It is assumed that network parameters and topology of the distribution network are available. The methods are applicable to a single fault as well as simultaneous faults and are applicable to both balanced and unbalanced networks. The methods utilize synchronized voltage and current phasor measurements to locate the fault. The methods are validated by simulation studies using the modified IEEE 34-Node Test System. Case studies have demonstrated that the methods are suitable for distribution systems with high penetration of distributed generations.


DYNA ◽  
2015 ◽  
Vol 82 (192) ◽  
pp. 141-149 ◽  
Author(s):  
Andres Felipe Panesso-Hernández ◽  
Juan Mora-Flórez ◽  
Sandra Pérez-Londoño

<p>The impedance-based approaches for fault location in power distribution systems determine a faulted line section. Next, these require of the estimation of the voltages and currents at one or both section line ends to exactly determine the fault location. It is a challenge because in most of the power distribution systems, measurements are only available at the main substation.  This document presents a modeling proposal of the power distribution system and an easy implementation method to estimate the voltages and currents at the faulted line section, using the measurements at the main substation, the line, load, transformer parameters and other serial and shunt connected devices and the power system topology. The approach here proposed is tested using a fault locator based on superimposed components, where the distance estimation error is lower than 1.5% in all of the cases. </p>


Author(s):  
M. Jawad Ghorbani ◽  
Hossein Mokhtari

This paper investigates the harmonic distortion and losses in power distribution systems due to the dramatic increase of nonlinear loads. This paper tries to determine the amount of the harmonics generated by nonlinear loads in residential, commercial and office loads in distribution feeders and estimates the energy losses due to these harmonics. Norton equivalent modeling technique has been used to model the nonlinear loads. The presented harmonic Norton equivalent models of the end user appliances are accurately obtained based on the experimental data taken from the laboratory measurements. A 20 kV/400V distribution feeder is simulated to analyze the impact of nonlinear loads on feeder harmonic distortion level and losses. The model follows a “bottom-up” approach, starting from end users appliances Norton equivalent model and then modeling residential, commercial and office loads. Two new indices are introduced by the authors to quantize the effect of each nonlinear appliance on the power quality of a distribution feeder and loads are ranked based on these new defined indices. The simulation results show that harmonic distortion in distribution systems can increase power losses up to 20%.