scholarly journals A new scheme of zero-sequence overcurrent protection of converter transformer based on zero-mode inrush current characteristics in station area

2022 ◽  
Vol 8 ◽  
pp. 1257-1263
Author(s):  
Yuanlin Pan ◽  
Zhichang Liu ◽  
Xin Yin ◽  
Wei Xi ◽  
Xianggen Yin ◽  
...  
Energies ◽  
2019 ◽  
Vol 12 (15) ◽  
pp. 2911 ◽  
Author(s):  
Wenbin Cao ◽  
Xianggen Yin ◽  
Yongxin Chen ◽  
Yuanlin Pan ◽  
Xiangyuan Yin ◽  
...  

In recent years, the zero-mode inrush current of high-impedance transformer with built-in high-voltage winding (T-Hin), which has large amplitude and decays slowly, causes the misoperation of zero-sequence overcurrent protection. Compared with magnetizing inrush current, the waveform of zero-mode inrush current is inconsistent and irregular, and few researches have proposed the mathematical analysis as well as the improved protection using waveform characteristics. In this paper, the mathematical expression of transformer zero-mode inrush current is derived. Further considering the parameter differences, the zero-mode inrush current of T-Hin is larger, which tends to cause the misoperation. The mathematical waveforms fit well with the recorded waveforms. Both recorded waveforms and mathematical waveforms in various conditions prove that the second harmonic ratio (the ratio between the second harmonic and first harmonic) of zero-mode inrush current is significant. Based on the above analysis, a criterion based on the second harmonic ratio restraint of zero-mode inrush current is proposed. If the second harmonic ratio exceeds the setting value, it is considered that the inrush current is generated and sends a signal to restrain the protection. The theoretical setting value of the proposed criterion and the practical engineering method for determining the setting value are obtained.


2021 ◽  
Author(s):  
Zhichang Liu ◽  
Xin Yin ◽  
Yuanlin Pan ◽  
Wei Xi ◽  
Xianggen Yin ◽  
...  

Author(s):  
Yuanlin Pan ◽  
Xin Yin ◽  
Xianggen Yin ◽  
Zhe Zhang ◽  
Lin Jiang ◽  
...  

Author(s):  
Wenbin Cao ◽  
Xianggen Yin ◽  
Zhe Zhang ◽  
Yuanlin Pan ◽  
Yuxue Wang ◽  
...  

Energies ◽  
2020 ◽  
Vol 13 (7) ◽  
pp. 1814
Author(s):  
Tao Zheng ◽  
Xinhui Yang ◽  
Xingchao Guo ◽  
Xingguo Wang ◽  
Chengqi Zhang

Through the analysis of the recovery inrush current generated by the external fault removal of the converter transformer, it is pointed out that the zero-sequence current caused by the recovery inrush may result in the saturation of the neutral current transformer (CT), whose measurement distortion contributes to the mis-operation of zero-sequence differential current protection. In this paper, a new scheme of zero-sequence differential current protection based on waveform correlation is proposed. By analyzing the characteristics of zero-sequence current under internal fault, external fault and external fault removal, the waveform correlation of the zero-sequence current measured at the terminal of the transformer and the zero-sequence current measured at the neutral point of the transformer is used for identification. The polarity of the CT is selected to guarantee the zero-sequence currents at the terminal and neutral point of the transformer exhibit a "ride through" characteristic under external fault, then the waveform similarity is high, and the correlation coefficient is positive. On the other hand, when internal fault occurs, zero-sequence current waveforms on both sides differ from each other largely, and the correlation coefficient is negative. Through a large number of simulations verified by PSCAD/EMTDC, this criterion can accurately identify internal and external faults, exempt from effects of the recovery inrush. Moreover, it presents certain ability for CT anti-saturation.