scholarly journals Zero-Sequence Differential Current Protection Scheme for Converter Transformer Based on Waveform Correlation Analysis

Energies ◽  
2020 ◽  
Vol 13 (7) ◽  
pp. 1814
Author(s):  
Tao Zheng ◽  
Xinhui Yang ◽  
Xingchao Guo ◽  
Xingguo Wang ◽  
Chengqi Zhang

Through the analysis of the recovery inrush current generated by the external fault removal of the converter transformer, it is pointed out that the zero-sequence current caused by the recovery inrush may result in the saturation of the neutral current transformer (CT), whose measurement distortion contributes to the mis-operation of zero-sequence differential current protection. In this paper, a new scheme of zero-sequence differential current protection based on waveform correlation is proposed. By analyzing the characteristics of zero-sequence current under internal fault, external fault and external fault removal, the waveform correlation of the zero-sequence current measured at the terminal of the transformer and the zero-sequence current measured at the neutral point of the transformer is used for identification. The polarity of the CT is selected to guarantee the zero-sequence currents at the terminal and neutral point of the transformer exhibit a "ride through" characteristic under external fault, then the waveform similarity is high, and the correlation coefficient is positive. On the other hand, when internal fault occurs, zero-sequence current waveforms on both sides differ from each other largely, and the correlation coefficient is negative. Through a large number of simulations verified by PSCAD/EMTDC, this criterion can accurately identify internal and external faults, exempt from effects of the recovery inrush. Moreover, it presents certain ability for CT anti-saturation.

Author(s):  
Azniza Ahmad ◽  
Mohammad Lufti Othman ◽  
Kurreemun Khudsiya Bibi Zainab ◽  
Hashim Hizam

Power transformer is the most expensive equipment in electrical power system that needs continuous monitoring and fast protection response. Differential relay is usually used in power transformer protection scheme. This protection compares the difference of currents between transformer primary and secondary sides, with which a tripping signal to the circuit breaker is asserted. However, when power transformers are energized, the magnetizing inrush current is present and due to its high magnitude, the relay mal-operates. To prevent mal-operation, methods revolving around the fact that the relay should be able to discriminate between the magnetizing inrush current and the fault current must be studied. This paper presents an Artificial Neural Network(ANN) based differential relay that is designed to enable the differential relay to correct its mal-operation during energization by training the ANN and testing it with harmonic current as the restraining element. The MATLAB software is used to implement and evaluate the proposed differential relay. It is shown that the ANN based differential relay is indeed an adaptive relay when it is appropriately trained using the Network Fitting Tool. The improved differential relay models also include a reset part which enables automatic reset of the relays. Using the techniques of 2nd harmonic restraint and ANN to design a differential relay thus illustrates that the latter can successfully differentiate between magnetizing inrush and internal fault currents. With the new adaptive ANN-based differential relay, there is no mal-operation of the relay during energization. The ANN based differential relay shows better performance in terms of its ability to differentiate fault against energization current. Amazingly, the response time, when there is an internal fault, is 1 ms compared to 4.5 ms of the conventional 2nd harmonic restraint based relay.


2015 ◽  
Vol 9 (1) ◽  
pp. 253-262
Author(s):  
Liu Zhongfu ◽  
Zhang Junxing ◽  
Shi Lixin ◽  
Yang Yaning

As for the wide application of arc suppression coil to the grounding in neutral point of mine high voltage grid, grid leakage fault rules and harmonic characteristics of the neutral point grounding system through arc suppression coil are analyzed, the selective leakage protection program “zero-sequence voltage starts, fifth harmonics of grid zerosequence voltage and zero-sequence current are extracted for phase comparison” is proposed, and corresponding fifth harmonic extraction circuit and power direction discrimination circuit are designed. The experimental results show that the protective principle applies not only to the neutral point insulated power supply system, but also to the power supply system in which neutral point passes arc suppression coil, which can solve selective leakage protection problems under different neutral grounding ways, improving the reliability of selective leakage and guaranteeing the stability of the action value.


2013 ◽  
Vol 732-733 ◽  
pp. 958-964
Author(s):  
Yao Zhao ◽  
Yu De Yang ◽  
Yan Hong Pan ◽  
Le Qi

The feasibility of transformer fast reenergizing with neutral point ungrounded after the external fault being removed is analyzed in this paper. By calculating overvoltage and discriminating magnetizing inrush current, it analyzes four ways to restore power of transformer and chooses the optimal strategy which is safe and time-saving. The result shows that in the case of transformer neutral point ungrounded, closing the low-voltage circuit side breaker before the high-voltage, which can effectively limit over-voltage in a safe range. The second harmonic characteristic of magnetizing waveform may disappear, while the intermittent angle characteristics are still significant. With the help of the intermittent angle principle, transformer differential protection may not misuse. The average time for each customer interruption is reduced from 40 minutes to 10 minutes and saves an hour for engineer on the way back and forth. It will greatly improve power supply reliability.


2021 ◽  
Vol 11 (11) ◽  
pp. 5076
Author(s):  
Hongyan Zhao ◽  
Yan Li ◽  
Fei Lin ◽  
Yian Yan

The balance control of neutral-point voltage (NPV) is important in the three-level converter. In this paper, this problem is studied by taking the VIENNA circuit as an example. The deviation of NPV is essentially caused by mismatch between the charging and discharging time of two series capacitors by the neutral-point current flowing into or out of the DC side. The unbalanced NPV will lead to unbalanced voltage stress of two capacitors and power switches and may cause overvoltage damage to both and also increase the total harmonic distortion (THD) and harmonic components in the AC current. In this paper, by analyzing the role and effect of a small-voltage vector on NPV, a control strategy based on the selection method of dynamical adjustment for a small vector is proposed. By judging the fluctuation of NPV, different small vectors are dynamically selected to act to adjust the NPV. For verification, the proposed strategy is compared with the traditional zero-sequence voltage injection (ZSV-J) method through simulation and experiment. Compared with ZSV-J, the THD of AC current is decreased by about 27.2%, the efficiency is increased by about 1.66%, and the adjustment speed of NPV is increased by about 50%. Therefore, the feasibility and advantages of the strategy are verified.


2015 ◽  
Vol 2015 ◽  
pp. 1-12 ◽  
Author(s):  
Yingjie Wang ◽  
Haiyuan Liu ◽  
Wenchao Wang ◽  
Kangan Wang

The neutral-point (NP) potential balance control in three-level neutral-point-clamped (NPC) back-to-back converter is a research nodus. Its current strategies are the same as the strategies of a single three-level NPC converter. But the strategies do not give full play to its advantages that the neutral-point current can only flow through the connected midlines in both sides of the converter but does not flow through the DC-bus capacitors. In this paper, firstly the NP potential model based on the NP current injected is proposed. It overcomes numerous variable constraints and mutual coupling in the conventional model based on the zero-sequence voltage injected. And then on this basis, three NP-potential balance control algorithms, unilateral control, bilateral independent control, and bilateral coordinated control, are proposed according to difference requirements. All of these algorithms use the midlines rather than the DC-bus capacitors to flow the NP current as much as possible. Their control abilities are further quantitatively analyzed and compared. Finally, simulation results verify the validity and effectiveness of these algorithms.


This paper presents a new innovative algorithm for Numerical Differential Relay design of transformer. Fault information is critical for operating and maintaining power networks. This algorithm provides accurate performance for transformer by which is independent of system conditions such as: External fault, Inrush current, CT saturation. Locating transformer faults quickly and accurately is very important for economy, safety and reliability point of view. Both fault-detection and protection indices are derived by using Numerical Differential Relay algorithm design of transformer. The embedded based differential and operating current measurement device is called numerical differential relay is among the most important development in the field of instantaneous fault operation. Numerical relay provides measurement of differential current and operating current at power transformer above 5MVA in substation. Simulation studies are carried out using MATLAB Software show that the proposed scheme provides a high accuracy and fast relay response in internal fault conditions. Current transformers form an important part of protective systems. Ideal Current Transformers (CTs) are expected to reflect the primary current faithfully on the secondary side. Under conditions the CT saturates, and hence it cannot reproduce the primary current faithfully. This paper deals with simulation methods for determining CT performance under different factor. A Simulink model has been developed to observe CT response under steady state w.r.t Burden, Turns ratio, Asymmetrical current, Hysteresis conditions. Thus, it is now possible to evaluate the CT performance under these factors