Numerical and experimental investigation of a helical coil heat exchanger for seawater-source heat pump in cold region

Author(s):  
Wandong Zheng ◽  
Huan Zhang ◽  
Shijun You ◽  
Tianzhen Ye
2022 ◽  
pp. 0958305X2110681
Author(s):  
Maryam Karami ◽  
Hajar Abdshahi

In this study, the transient performance of a qanat source heat pump is investigated using a TRNSYS-MATLAB co-simulator. The water/ethylene glycol-to-air compression heat pump and the helical coil heat exchanger, which is used to inject heat to or to extract heat from the qanat water, are mathematically modeled in matrix laboratory (MATLAB), and then, coupled to transient systems simulation (TRNSYS) model to evaluate the system transient performance and calculate the heating and cooling loads of the case study building. Comparison of the performance of the qanat source heat pump with an air source heat pump showed that the coefficient of performance of the qanat source heat pump is at least 5% and at most 34% higher than that of the air source heat pump. By increasing the flow rate of the working fluid in the helical coil heat exchanger from 2 L/min to 8 L/min, the coefficient of performance of the qanat source heat pump increases at least 12% and at most 34.1%. The maximum increase in energy efficiency ratio and free energy ratio of the system by the similar increase in the flow rate is 46.4% and 24.8%, respectively. The exergy analysis of the qanat source heat pump reveals that the minimum and maximum exergy efficiency of the system is 32% and 85.5%, respectively. The findings also indicate that the most exergy destruction occurs in the condenser in heating mode and in the evaporator in cooling mode.


Sign in / Sign up

Export Citation Format

Share Document