A peak current limit control technique in low-voltage ride through operation of the star-connected cascaded H-bridges converter

Author(s):  
Chia-Tse Lee ◽  
Hsin-Chih Chen ◽  
Ching-Wei Wang ◽  
Ping-Heng Wu ◽  
Ching-Hsiang Yang ◽  
...  
Energies ◽  
2021 ◽  
Vol 14 (19) ◽  
pp. 6168
Author(s):  
Markel Zubiaga ◽  
Carmen Cardozo ◽  
Thibault Prevost ◽  
Alain Sanchez-Ruiz ◽  
Eneko Olea ◽  
...  

With an increasing capacity of inverter-based generation and with a 100% renewable energy power system on the horizon, grid forming converters have the potential to become the prevalent control mode in the grid. Thus, the correct performance of these devices is going to be crucial for system stability and security of supply. Most research related to the grid-forming control is focused on normal operating conditions, although significant effort has been devoted to current limitation strategies to ensure Low Voltage Ride Through (LVRT) capability. However, most contributions usually consider only balanced faults. This paper, proposes a new current limiting method based on the well-known threshold virtual impedance (TVI) that keeps the voltage source behaviour associated to the grid forming (GFM) capability, even when the current limit is reached, while reducing the voltage unbalance according to user-defined settings.