In this paper, we introduced a high cost performance design of air flow control system consisting of a programmable computer controller (PCC) and 72 inverters. PCC communicates with all the inverters using USS protocol via RS485 bus, and the real-time performance of USS communication was analyzed for this system. The commissioning and analysis show that the total communication cycle time of a subnet is less than 500ms and the maximum deviation of the inverter frequency is 0.01Hz. This system can meet the requirements of high performance carbon fiber production.