scholarly journals Analisis Pengaruh Ketidakseimbangan Beban dan Harmonisa Terhadap Arus Netral Pada Trafo Distribusi 8 Kapasitas 500 KVA di PPSDM Migas Cepu

Author(s):  
Riki Khomarudin ◽  
Lukman Subekti

Distribution transformer 8 at PPSDM Migas Cepu has a capacity of 500 kVA with load connected to boiler and refinery. The loading connected to the distribution transformer 8 is the majority of the 3-phase motor pump load and some 1-phase pump motors. In this case study measurements were made using the ampere pliers as the hypothesis of the current of each phase. From the measurement result there is imbalance of load between channel and also there is current value of neutral conductor side. And to know the content of harmonics on the distribution transformer, then measured with a power quality analyzer.The result of measurement with fluke quality 436 type fluke quality got result of measurement that current value at neutral conductor side equal to 14A. The value of load imbalance between conductor obtained by value of channel current R equal to 346A, in channel S equal to 306A, and in channel T equal to 318A. The THD value of the current obtained from the measurement with the power quality analyzer on the conductor side of R is 3.4%, on the conductor side S of 3.0%, and on the conductor side of T is 3.0%, and in the neutral channel is the greatest value of 29%. In the analysis of this chapter we get the result of imbalance loads of 4.6%, with the average loading of 45% of the total capacity of the transformer

2009 ◽  
Vol 1 (1) ◽  
pp. 49-59
Author(s):  
Riza Widia ◽  
Herisajani Herisajani ◽  
Witrionanda Witrionanda

Loads of electricity utility consists of linear loads and non linear loads. The non linear loads for example TV, personal computer, VCD player, microwave and fluorescent lamp using electronics ballast. Loads with non linear characteristics become harmonic current source to electricity utility. Condition prediction used statistic linear comparison based on load power to THDi (Distortion of Harmonic Current). Measurement result using power quality analyzer and etap 4.0 (Fluke 43B) find typical THDi. The calculation and measurement result of PF and THD to loads of electricity utility show the differences less than 5%. However power factor formulation and distortions of harmonic current is valid


2016 ◽  
Vol 834 ◽  
pp. 205-210
Author(s):  
Elena Loredana Terzea ◽  
Antonia Cristina Barascu ◽  
Iulian Razvan Soare

Batch processes includes paint manufacturing, food processing, pharmaceutical industry, etc. The paper focuses on the process of paint manufacturing. The main contribution is the design of the current value stream mapping, very useful to understand the causes of waste and lead-time. This paper points out the necessity of applying lean methods within automotive industry, sector of bumpers painting and assembly, based on a real case-study.