Optimal temperature sensor placement in buildings with buoyancy-driven natural ventilation using computational fluid dynamics and uncertainty quantification

2021 ◽  
pp. 108496
Author(s):  
Chen Chen ◽  
Catherine Gorlé
Author(s):  
Andrea Beck ◽  
Jakob Dürrwächter ◽  
Thomas Kuhn ◽  
Fabian Meyer ◽  
Claus-Dieter Munz ◽  
...  

Author(s):  
Peter Abdo ◽  
Rahil Taghipour ◽  
B. P. Huynh

Abstract Windcatcher has been used over centuries for providing natural ventilation using wind power, it is an effective passive method to provide healthy and comfortable indoor environment. The windcatcher’s function is based on the wind and on the stack effect resulting from temperature differences. Generally, it is difficult for wind to change its direction, and enter a room through usual openings, the windcatcher is designed to overcome such problems since they have vertical columns to help channel wind down to the inside of a building. The efficiency of a windcatcher is maximized by applying special forms of opening and exit. The openings depend on the windcatcher’s location and on its cross sectional area and shape such as square, rectangular, hexagonal or circular. In this study the effect of the inlet design is investigated to achieve better air flow and increase the efficiency of windcatchers. To achieve this, CFD (computational fluid dynamics) tool is used to simulate the air flow in a three dimensional room fitted with a windcatcher based on the different inlet designs. The divergent inlet has captured the highest air flow with a difference of approximately 3% compared to the uniform inlet and 5% difference compared to the bulging-convergent inlet.