Flow Boiling in Horizontal Tubes: Part 2—New Heat Transfer Data for Five Refrigerants

1998 ◽  
Vol 120 (1) ◽  
pp. 148-155 ◽  
Author(s):  
N. Kattan ◽  
J. R. Thome ◽  
D. Favrat

A summary of a comprehensive experimental study on flow boiling heat transfer is presented for five refrigerants (R134a, R123, R402A, R404A, and R502) evaporating inside plain, horizontal, copper tube test sections. The test data were obtained for both 12.00 mm and 10.92 mm diameters using hot water as the heating source. Besides confirming known trends in flow boiling heat transfer data as a function of test variables, it was also proven that the heat flux level at the dryout point at the top of the tube in annular flow has a very significant downstream effect on heat transfer coefficients in the annular flow regime with partial dryout.

1999 ◽  
Author(s):  
Lixin Cheng ◽  
Tingkuan Chen

Abstract Experiments of upward flow boiling heat transfer with water in a vertical smooth tube and a tube with axial micro-grooves were respectively conducted. Both of the tested tubes have a length of 2.5 m, an inner diameter of 15 mm and an outlet diameter of 19 mm. The tube with axial micro grooves has many micro rectangle grooves in its inner wall along the axial direction. The grooves have a depth of 0.5 mm and a width of 0.3 mm. The tests were performed at an absolute pressure of 6 bar. The heat flux ranged from 0 to 550 kW/m2 and the mass flux was selected at 410, 610 and 810 kg/m2s, respectively. By comparison, flow boiling heat transfer coefficients in the enhanced tube are 1.6 ∼ 2.7 fold that in the smooth tube while the frictional pressure drop in the enhanced tube is slightly greater than that in the smooth tube. The augmentation of flow boiling heat transfer in the tube with axial micro-grooves is apparent. Based on the experimental data, a correlation of flow boiling heat transfer is proposed for the enhanced tube. Finally, the mechanisms of heat transfer enhancement are analyzed.


2009 ◽  
Vol 131 (9) ◽  
Author(s):  
Chang Yong Park ◽  
Pega Hrnjak

Abstract C O 2 flow boiling heat transfer coefficients and pressure drop in a 3.5mm horizontal smooth tube are presented. Also, flow patterns were visualized and studied at adiabatic conditions in a 3mm glass tube located immediately after a heat transfer section. Heat was applied by a secondary fluid through two brass half cylinders to the test section tubes. This research was performed at evaporation temperatures of −15°C and −30°C, mass fluxes of 200kg∕m2s and 400kg∕m2s, and heat flux from 5kW∕m2 to 15kW∕m2 for vapor qualities ranging from 0.1 to 0.8. The CO2 heat transfer coefficients indicated the nucleate boiling dominant heat transfer characteristics such as the strong dependence on heat fluxes at a mass flux of 200kg∕m2s. However, enhanced convective boiling contribution was observed at 400kg∕m2s. Surface conditions for two different tubes were investigated with a profilometer, atomic force microscope, and scanning electron microscope images, and their possible effects on heat transfer are discussed. Pressure drop, measured at adiabatic conditions, increased with the increase of mass flux and quality, and with the decrease of evaporation temperature. The measured heat transfer coefficients and pressure drop were compared with general correlations. Some of these correlations showed relatively good agreements with measured values. Visualized flow patterns were compared with two flow pattern maps and the comparison showed that the flow pattern maps need improvement in the transition regions from intermittent to annular flow.


Author(s):  
Kwang-Hyun Bang ◽  
Kun-Eui Hong ◽  
In-Seon Hwang

This paper reports an experimental study on flow boiling of water in a minichannel. Flow boiling heat transfer coefficients and pressure drops were measured and the data were compared with existing correlations. The effect of pressure was the major objectives in this study and the range of pressure was 1 to 18 bars. The experimental apparatus consisted mainly of a minichannel test section, gear pump, pre-heater, pressurizer, condenser and evaporator. The evaporator was used for variation of vapor quality at the inlet of test section. The pressurizer controls the desired system pressure. The test section is a round tube of 1.73 mm inside diameter, made of 316 stainless steel. The test section and the evaporator tubes were heated by DC electric current through the tubes. The measured flow boiling heat transfer coefficients showed two distinct regions; relatively high heat transfer coefficients at low vapor quality and lower heat transfer coefficients at higher vapor quality. This observation implies the change of flow regime, slug to annular flow. Comparisons of the experimental data and the prediction of correlations (Gungor & Winterton, 1987; Tran et al., 1996; Kandlikar, 2003) showed large discrepancy in both regions.


Sign in / Sign up

Export Citation Format

Share Document