Flow Boiling Heat Transfer, Pressure Drop, and Flow Pattern for CO2 in a 3.5mm Horizontal Smooth Tube

2009 ◽  
Vol 131 (9) ◽  
Author(s):  
Chang Yong Park ◽  
Pega Hrnjak

Abstract C O 2 flow boiling heat transfer coefficients and pressure drop in a 3.5mm horizontal smooth tube are presented. Also, flow patterns were visualized and studied at adiabatic conditions in a 3mm glass tube located immediately after a heat transfer section. Heat was applied by a secondary fluid through two brass half cylinders to the test section tubes. This research was performed at evaporation temperatures of −15°C and −30°C, mass fluxes of 200kg∕m2s and 400kg∕m2s, and heat flux from 5kW∕m2 to 15kW∕m2 for vapor qualities ranging from 0.1 to 0.8. The CO2 heat transfer coefficients indicated the nucleate boiling dominant heat transfer characteristics such as the strong dependence on heat fluxes at a mass flux of 200kg∕m2s. However, enhanced convective boiling contribution was observed at 400kg∕m2s. Surface conditions for two different tubes were investigated with a profilometer, atomic force microscope, and scanning electron microscope images, and their possible effects on heat transfer are discussed. Pressure drop, measured at adiabatic conditions, increased with the increase of mass flux and quality, and with the decrease of evaporation temperature. The measured heat transfer coefficients and pressure drop were compared with general correlations. Some of these correlations showed relatively good agreements with measured values. Visualized flow patterns were compared with two flow pattern maps and the comparison showed that the flow pattern maps need improvement in the transition regions from intermittent to annular flow.

Author(s):  
C. Y. Park ◽  
P. S. Hrnjak

In this study, flow boiling heat transfer coefficients and flow patterns CO2 are examined in horizontal smooth tubes with inner diameter 6.1 and 3.5 mm at low temperatures. In order to measure the heat transfer coefficients, the test tube was heated by two brass pieces maintained a higher temperature than CO2 by a secondary fluid. Flow visualization was carried out at adiabatic conditions. This research was performed at evaporation temperatures of -15 and -30 °C, mass flux from 100 to 400 kg/m2 s, and heat flux from 5 to 15 kW/m2 for vapor qualities ranging from 0.1 to 0.8. The CO2 heat transfer coefficients for the 6.1 and 3.5 mm tubes had nucleate boiling dominant heat transfer characteristics such as the strong dependence on heat fluxes. However, enhanced convective boiling contribution was presented for the 3.5 mm tube at 400 kg/m2 s. The presented heat transfer coefficients indicated the reduction of heat transfer coefficient as mass flux increased at low quality regions and also showed that dryout did not occur until the high quality region of 0.8, for mass fluxes of 200 and 400 kg/m2 s. The measured heat transfer coefficients were compared with predicted values with some general correlations to predict flow boiling heat transfer coefficients. The pictures of visualized flow patterns were presented and the flow patterns were compared with a flow pattern map. They were used to explain the relation between the flow boiling heat transfer coefficient and vapor quality at the mass flux of 100 kg/m2 s.


Author(s):  
Cheol Huh ◽  
Moo Hwan Kim

With a single microchannel and a series of microheaters made with MEMS technique, two-phase pressure drop and local flow boiling heat transfer were investigated using deionized water in a single horizontal rectangular microchannel. The test microchannel has a hydraulic diameter of 100 μm and length of 40 mm. A real time observation of the flow patterns with simultaneous measurement are made possible. Tests are performed for mass fluxes of 90, 169, and 267 kg/m2s and heat fluxes of from 100 to 600 kW/m2. The experimental local flow boiling heat transfer coefficients and two-phase frictional pressure gradient are evaluated and the effects of heat flux, mass flux, and vapor qualities on flow boiling are studied. Both the evaluated experimental data are compared with existing correlations. The experimental heat transfer coefficients are nearly independent on mass flux and the vapor quality. Most of all correlations do not provide reliable heat transfer coefficients predictions with vapor quality and prediction accuracy. As for two-phase pressure drop, the measured pressure drop increases with the mass flux and heat flux. Most of all existing correlations of two-phase frictional pressure gradient do not predict the experimental data except some limited conditions.


Author(s):  
Benjamin J. Jones ◽  
Suresh V. Garimella

The influence of surface roughness on flow boiling heat transfer and pressure drop in microchannels is experimentally explored. The microchannel heat sink employed in the study consists of ten parallel, 25.4 mm long channels with nominal dimensions of 500×500 μm2. The channels were produced by saw-cutting. Two of the test piece surfaces were roughened to varying degrees with electrical discharge machining (EDM). The roughness average Ra varied from 1.4 μm for the as-fabricated, saw-cut surface to 3.9 μm and 6.7 μm for the two roughened EDM surfaces. Deionized water was used as the working fluid. The experiments indicate that the surface roughness has little influence on boiling incipience and only a minor impact on saturated boiling heat transfer coefficients at lower heat fluxes. For wall heat fluxes above 1500 kW/m2, the two EDM surfaces (3.9 μm and 6.7 μm) have similar heat transfer coefficients that were 20–35% higher than those measured for the saw-cut surface (1.4 μm). A modified Bertsch et al. [2009, “A Composite Heat Transfer Correlation for Saturated Flow Boiling in Small Channels,” Int. J. Heat Mass Transfer, 52, pp. 2110–2118] correlation was found to provide acceptable predictions of the flow boiling heat transfer coefficient over the range of conditions tested. Analysis of the pressure drop measurements indicates that only the roughest surface (6.7 μm) has an adverse effect on the two-phase pressure drop.


2005 ◽  
Vol 127 (12) ◽  
pp. 1305-1312 ◽  
Author(s):  
Chang Yong Park ◽  
Pega S. Hrnjak

Flow boiling heat transfer coefficients of CO2 are measured in a horizontal smooth tube with inner diameter 6.1mm. The test tube is heated by a secondary fluid maintaining constant wall temperature conditions. Heat transfer coefficients are measured at evaporation temperatures of −15 and −30°C, mass flux from 100to400kg∕m2s, and heat flux from 5to15kW∕m2 for qualities (vapor mass fractions) ranging from 0.1 to 0.8. The characteristics of CO2 flow boiling are explained by CO2 properties and flow patterns. The measured CO2 heat transfer coefficients are compared to other published data. Experiments with R22 were also conducted in the same system and the results show that the heat transfer coefficients for CO2 are 40 to 150% higher than for R22 at −15°C and low mass flux of 200kg∕m2s mostly due to the characteristics of CO2 nucleate boiling. The presented CO2 heat transfer coefficients indicate the reduction of heat transfer coefficient as mass flux increases at low quality regions and also show that dryout does not occur until the high quality region of 0.8, for mass fluxes of 200 and 400kg∕m2s. The Gungor and Winterton correlation gives a relatively good agreement with measured data; however it deviates more at lower evaporation temperature and high mass flux conditions.


Author(s):  
Kwang-Hyun Bang ◽  
Kun-Eui Hong ◽  
In-Seon Hwang

This paper reports an experimental study on flow boiling of water in a minichannel. Flow boiling heat transfer coefficients and pressure drops were measured and the data were compared with existing correlations. The effect of pressure was the major objectives in this study and the range of pressure was 1 to 18 bars. The experimental apparatus consisted mainly of a minichannel test section, gear pump, pre-heater, pressurizer, condenser and evaporator. The evaporator was used for variation of vapor quality at the inlet of test section. The pressurizer controls the desired system pressure. The test section is a round tube of 1.73 mm inside diameter, made of 316 stainless steel. The test section and the evaporator tubes were heated by DC electric current through the tubes. The measured flow boiling heat transfer coefficients showed two distinct regions; relatively high heat transfer coefficients at low vapor quality and lower heat transfer coefficients at higher vapor quality. This observation implies the change of flow regime, slug to annular flow. Comparisons of the experimental data and the prediction of correlations (Gungor & Winterton, 1987; Tran et al., 1996; Kandlikar, 2003) showed large discrepancy in both regions.


2013 ◽  
Vol 135 (2) ◽  
Author(s):  
YanFeng Fan ◽  
Ibrahim Hassan

Flow boiling heat transfer in a horizontal microtube with inlet restriction (orifice) under uniform heating condition is experimentally investigated using FC-72 as working fluid. A stainless steel microtube with an inner diameter of 889 μm is selected as main microtube. Two microtubes with smaller diameters are assembled at the inlet of main microtube to achieve the restriction ratios of 50% and 20%. The experimental measurement is carried out at mass fluxes ranging from 160 to 870 kg/m2·s, heat fluxes varying from 6 to 170 kW/m2, inlet temperatures of 23 and 35 °C, and saturation pressures of 10 and 45 kPa. The effects of the orifices on two-phase pressure drop, critical heat flux (CHF), and flow boiling heat transfer coefficient are studied. The results show that the pressure drop caused by the orifice takes a considerable portion in the total pressure drop at low mass fluxes. This ratio decreases as the vapor quality or mass flux increases. The difference of normal critical heat flux in the microtubes with different orifice sizes is negligible. In the aspect of flow boiling heat transfer, the orifice is able to enhance the heat transfer at low mass flux and high saturation pressure, which indicates the contribution of orifice in the nucleate boiling dominated regime. However, the effect of orifice on flow boiling heat transfer is negligible in the forced convective boiling dominated regime.


Author(s):  
Fernando Neves Quintino dos Santos ◽  
Matheus Barroso ◽  
Juan Jose Garcia Pabon ◽  
Hélio Augusto Goulart Diniz ◽  
Paulo Eduardo Lopes Barbieri