Performance Investigation of Cascade Refrigeration System Using CO2 and Mixtures

2015 ◽  
Vol 23 (03) ◽  
pp. 1550022 ◽  
Author(s):  
Nourheine Jemni ◽  
Mouna Elakhdar ◽  
Ezzedine Nehdi ◽  
Lakdar Kairouani

This paper presents reports on simulation and comparative analysis of single stage vapor compression refrigeration system and cascade systems using carbon dioxide, hydrocarbons (HCs) and CO2/HCs mixture. Thermodynamic parameters of fluids are given using the software REFPROP 9.0. To select the most suitable HCs, three criteria have been fixed: Tc, Tt and Tb. It is found that the HCs chosen in low-stage are propane, propylene and ethane and those for the high-stage are propane, propylene and isobutane. The fraction mixture in the two loops has been varied and results are compared with single stage and cascade systems using CO2 and R22. The fraction x[Formula: see text] is varied in the two loops. Results are compared for single and cascade systems using CO2 and R22. For the single stage system, we find for xCO2 = 0.5, an improvement of COP of 14% for CO2/propane mixture and 36% for the CO2/propylene mixture. It is found that for xCO2 = 0.3, cascade system using propane/CO2 mixtures presents a COP lower than that of cascade system using pure CO2. About of 70% of unfriendly fluids like CFCs and HCFCs can be replaced with CO2, without affecting the performance of cascade refrigeration systems.

Energies ◽  
2021 ◽  
Vol 14 (4) ◽  
pp. 946
Author(s):  
Bartosz Gil ◽  
Anna Szczepanowska ◽  
Sabina Rosiek

In this work, which is related to the current European Parliament Regulation on restrictions affecting refrigeration, four new three-component refrigerants have been proposed; all were created using low Global Warming Potential(GWP) synthetic and natural refrigerants. The considered mixtures consisted of R32, R41, R161, R152a, R1234ze (E), R1234yf, R1243zf, and RE170. These mixtures were theoretically tested with a 10% step in mass fraction using a triangular design. The analysis covered two theoretical cooling cycles at evaporating temperatures of 0 and −30 °C, and a 30 °C constant condensing temperature. The final stage of the work was the determination of the best mixture compositions by thermodynamic and operational parameters. R1234yf–R152a–RE170 with a weight share of 0.1/0.5/0.4 was determined to be the optimal mixture for potentially replacing the existing refrigerants.


2019 ◽  
Vol 15 ◽  
pp. 100531 ◽  
Author(s):  
Santiphap Nakkaew ◽  
Thunyawat Chitipalungsri ◽  
Ho Seon Ahn ◽  
Dong-Wook Jerng ◽  
Lazarus Godson Asirvatham ◽  
...  