EXHAUST-TUBELESS TECHNOLOGICAL PROCESSES FOR CERAMIC-METAL HIGH-VOLTAGE VACUUM ARC EXTINJUISH CHAMBERS PRODUCTION (VDK-110)

Author(s):  
V. G. Gorohova ◽  
◽  
A. T. Rott ◽  
A. I. Kudyukin ◽  
E. N. Moos ◽  
...  
2018 ◽  
Vol 10 (2) ◽  
pp. 02035-1-02035-6
Author(s):  
O. V. Sobol ◽  
◽  
А. А. Postelnyk ◽  
R. P. Mygushchenko ◽  
V. F. Gorban ◽  
...  

Author(s):  
С.Г. Давыдов ◽  
А.Н. Долгов ◽  
А.В. Корнеев ◽  
Р.Х. Якубов

AbstractThe process of electron instability development and propagation of a cathode electron beam and anomalous ion beam, followed by outburst of current in the initial stage of arc discharge was observed in rarefied plasma cloud of high-voltage vacuum diode. These events are consistent with the model of anomalous ion acceleration in interelectrode plasma at the spark stage of vacuum arc discharge.


2019 ◽  
Vol 6 (1) ◽  
pp. 19-22
Author(s):  
S. Giere ◽  
T. Heinz ◽  
A. Lawall ◽  
C. Stiehler ◽  
E. D. Taylor ◽  
...  

During the development of a commercial vacuum interrupter for application in HV (high voltage) switchgear at a rated voltage of 145kV, we investigated the behavior of vacuum arcs controlled by axial magnetic fields (AMF). AMF arc control is already extensively used in medium voltage (1-52kV) applications, the key difference is the 2-3 times larger contact gap and the corresponding reduction of the AMF strength for HV applications. We conducted several stress tests with short circuit currents up to 40kA, thus not only testing the interrupting capability, but also the electrical endurance of such a contact system. We also investigated the dielectric behavior of the vacuum interrupter by testing the capacitive switching duty. Overall, the contacts were used in about 40 operations at high currents. Despite this large number of operations, they showed a minimal amount of contact erosion and damage and demonstrated behavior very similar to the extensive experience with MV vacuum interrupters. In line with simulation results, we conclude that even at high contact gaps and currents, a diffuse vacuum arc was maintained which distributed the arc energy evenly over the contacts.


2012 ◽  
Vol 54 (3-4) ◽  
pp. 195-203 ◽  
Author(s):  
O. V. Sobol’ ◽  
A. A. Andreev ◽  
S. N. Grigoriev ◽  
V. F. Gorban’ ◽  
M. A. Volosova ◽  
...  

Shinku ◽  
2007 ◽  
Vol 50 (5) ◽  
pp. 341-344
Author(s):  
Shaoyong CHENG ◽  
Shixin XIU ◽  
Jimei WANG ◽  
Zhengchao SHEN

1994 ◽  
Author(s):  
R. Y. Ivanov ◽  
S. V. Puzanov ◽  
Y. M. Yashnov

2003 ◽  
Vol 29 (6) ◽  
pp. 534-537
Author(s):  
A. V. Zharinov ◽  
V. P. Shumilin
Keyword(s):  

Sign in / Sign up

Export Citation Format

Share Document