The Research Based on Zero Sequence Energy to the Line Selection in Distribution Network

2012 ◽  
Vol 614-615 ◽  
pp. 846-849
Author(s):  
Shu Tian ◽  
Jin Peng He ◽  
Yu Zheng

When single phase-to-ground fault happened in power network with arc suppression coil grounded, capacitor current through fault point is compensated and reduced by installing arc suppression coil. Zero-sequence current’s amplitude and phase of fault lines and sound lines are so similar that it increases the difficulty of selecting the fault line. But the resistance component of zero sequence current has no relationship with the arc extinguishing coil compensation, absolute value of resistance component to the fault lines show the maximum, and zero sequence current’s polarity of fault lines is contrary to sound lines. In this paper, because of the characteristic of resistance component, a method is put forward based on zero sequence energy to the line selection in distribution network, it import auto-reclosing techniques into the line selection. The principle is verified by MATLAB simulator. It has high accuracy to select the fault line with this method.

2012 ◽  
Vol 217-219 ◽  
pp. 2629-2633 ◽  
Author(s):  
Yang Liu ◽  
Zhang Bao Chen ◽  
Lin Ye

In order to find new fault line selection method of single-phase distribution network, First parallel resistance in the neutral point in order to increase the transient component of the fault line, obtained the line energy after the failure through the integral transform , initially selected probable fault lines , on this basis, decompose all the transient zero sequence currents in every line by separation based on nicer separate frequency characteristic of wavelet packets, to accurately determine the greatest fault line by the characteristic that the value of second singular point generated by zero sequence current is maximum and its polarity is opposite to the other normal lines, simulation results show the effectiveness and correctness of the method. So the method for detection of the fault line based on wavelet packets and the compare of energy is new and effective.


2021 ◽  
Vol 2095 (1) ◽  
pp. 012029
Author(s):  
Yicen Liu ◽  
Xiaojiang Liu ◽  
Songhai Fan ◽  
Xiaomin Ma ◽  
Sijing Deng

Abstract In view of the complex characteristics of nonlinearity and non-stableness of the zero-order current of each line after the single-phase ground fault of the distribution network, a distribution network fault selection method based on Sooty Tern Optimization Algorithm(STOA) and the combination of support vector machine is proposed. At first, the zero-sequence current before and after fault is obtained, then five kinds of IMFs including different components are obtained by ensemble empirical mode decomposition, and the energy entropy of the fault transient zero-sequence current is obtained by Hilbert transform, the results of training and testing are obtained by inputting the feature vector. The simulation results show that the accuracy of the proposed line selection model is 97.5%.