Cumulative deformation analysis of transformer winding under short-circuit fault using 3-D FEM

Author(s):  
Hai Jun Zhang ◽  
Shu Hong Wang ◽  
Song Wang
2012 ◽  
Vol 268-270 ◽  
pp. 1341-1344
Author(s):  
Hong Kui Li

This research studies the displacement on the windings of transformer due to multiple short-circuit forces. The power transformer winding deformations cumulative impact of multiple short-circuits are studied. the cumulative impact of multiple short-circuit deformation of laminated cylindrical shell with stiffeners model is established, the impact of accumulated deformation of multiple short-circuit of transformer winding is calculated with large deformation elastic-plastic theory , the text introduced by the theoretical formula for power transformer windings of the elastic-plastic deformation analysis of and winding to determine the stability have great significance, To verify the computation results, they are compared with those obtained using ANSYS software simulation.


2014 ◽  
Vol 24 (3) ◽  
pp. 1-4 ◽  
Author(s):  
Haijun Zhang ◽  
Bin Yang ◽  
Weijie Xu ◽  
Shuhong Wang ◽  
Guolin Wang ◽  
...  

Author(s):  
Nurul Farahwahida Md Yasid ◽  
A. A. Alawady ◽  
M. F. M. Yousof ◽  
S. Al-Ameri ◽  
M. S. Kamarudin

Sweep frequency response analysis (SFRA) is a reliable method for detection and diagnosis of faults in the active part of transformers. However, although SFRA is widely employed, the interpretation of SFRA signature is still a challenge and require experts to analyse them. This is due to lack of guideline and standard for SFRA signature interpretation and clarification. This paper presents the interpretation of SFRA signature by classification and quantification on inter-turn short circuit fault on the transformer winding. The short-circuited turns fault on HV winding phase “A” was practically simulated on three different units of three-phase transformers. The results of simulated fault are presented and discussed. A conclusion was drawn which provides the interpretation of the SFRA response due to inter-turn short circuit fault case by using a statistical indicator which is NCEPRI algorithm.


Sign in / Sign up

Export Citation Format

Share Document