Identification of Grid Impedance for Purposes of Voltage Feedback Active Filtering

2004 ◽  
Vol 2 (1) ◽  
pp. 6-10 ◽  
Author(s):  
A. Tarkiainen ◽  
R. Pollanen ◽  
M. Niemela ◽  
J. Pyrhonen
2017 ◽  
Vol 2017 ◽  
pp. 1-11
Author(s):  
Zeyu Shi ◽  
Yingpin Wang ◽  
Yunxiang Xie ◽  
Lanfang Li ◽  
Xiaogang Xu

Active power filter (APF) is the most popular device in regulating power quality issues. Currently, most literatures ignored the impact of grid impedance and assumed the load voltage is ideal, which had not described the system accurately. In addition, the controllers applied PI control; thus it is hard to improve the compensation quality. This paper establishes a precise model which consists of APF, load, and grid impedance. The Bode diagram of traditional simplified model is obviously different with complete model, which means the descriptions of the system based on the traditional simplified model are inaccurate and incomplete. And then design exact feedback linearization and quasi-sliding mode control (FBL-QSMC) is based on precise model in inner current loop. The system performances in different parameters are analyzed and dynamic performance of proposed algorithm is compared with traditional PI control algorithm. At last, simulations are taken in three cases to verify the performance of proposed control algorithm. The results proved that the proposed feedback linearization and quasi-sliding mode control algorithm has fast response and robustness; the compensation performance is superior to PI control obviously, which also means the complete modeling and proposed control algorithm are correct.