This paper analyzes the object-oriented modeling technology of IEC 61850 standard and the modeling steps of condition monitoring intelligent electronic devices (IED). Aiming at the problem of the existing configuration tools poor scalability for the IEC 61850 standard, a new design method of the IED configuration tool is brought up. Information model of transformer condition monitoring IED is established including logical device (LD), logical node (LN), data object (DO), data attribute (DA), dataset and report control block with the method mentioned above, and described with substation configuration description language.