scholarly journals Multiple Spatiotemporal Characteristics-Based Zonal Voltage Control for High Penetrated PVs in Active Distribution Networks

Energies ◽  
2020 ◽  
Vol 13 (1) ◽  
pp. 249 ◽  
Author(s):  
Chuanliang Xiao ◽  
Lei Sun ◽  
Ming Ding

The penetration of photovoltaic (PV) outputs brings great challenges to optimal operation of active distribution networks (ADNs), especially leading to more serious overvoltage problems. This study proposes a zonal voltage control scheme based on multiple spatiotemporal characteristics for highly penetrated PVs in ADNs. In the spatial domain, a community detection algorithm using a reactive/ active power quality function was introduced to partition an ADN into sub-networks. In the time domain, short-term zonal scheduling (SZS) with 1 h granularity was drawn up based on a cluster. The objective was to minimize the supported reactive power and the curtailed active power in reactive and active power sub-networks. Additionally, a real-time zonal voltage control scheme (RZVC) with 1 min granularity was proposed to correct the SZS rapidly by choosing and controlling the key PV inverter to regulate the supported reactive power and the curtailed active power of the inverters to prevent the overvoltage in each sub-network. With the time domain cooperation, the proposed method could achieve economic control and avoid overvoltage caused by errors in the forecast data of the PVs. For the spatial domain, zonal scheduling and zonal voltage control were carried out in each cluster, and the short-term scheduling and voltage controlling problem of the ADN could then be decomposed into several sub-problems. This could simplify the optimization and control which can reduce the computing time. Finally, an actual 10kV, 103-node network in Zhejiang Province of China is employed to verify the effectiveness and feasibility of the proposed approach.

Energies ◽  
2020 ◽  
Vol 13 (11) ◽  
pp. 2849
Author(s):  
Seok-Il Go ◽  
Sang-Yun Yun ◽  
Seon-Ju Ahn ◽  
Hyun-Woo Kim ◽  
Joon-Ho Choi

The voltage and reactive power control (Volt/VAR Control, VVC) in distribution networks has become a challenging issue with the increasing utilization of distributed generations (DGs). In this paper, a heuristic-based coordinated voltage control scheme that considers distribution voltage control devices, i.e., on-load tap changers (OLTC) and step voltage regulators (SVR), as well as reactive power control devices, i.e., DGs, are proposed. Conventional voltage control methods using non-linear node voltage equations require complex computation. In this paper, the formulation of simplified node voltage equations accounting for changes in tap position of distribution voltage control devices and reactive power changes of reactive power control devices are presented. A heuristic coordinated voltage control scheme using the proposed simplified node voltage equations is proposed. A coordinated voltage control scheme to achieve voltage control for nominal voltage and conservative voltage reduction (CVR) is presented. The results of the proposed schemes are compared with the results from the quadratic optimization method to confirm that the proposed schemes yields suitably similar results. Furthermore, a tap scheduling method is proposed to reduce the number of tap changes while controlling network voltage. The tap position is readjusted using a voltage control performance index (PI). Simulation results confirm that when using this method the number of tap changes is reduced. The proposed scheme not only produces reasonable performance in terms of control voltage of networks but also reduces the number of tap changes made by OLTC. The proposed control method is an alternative candidate for a system to be applied to practical distribution networks due to its simplified calculations and robust performance.


Energies ◽  
2019 ◽  
Vol 12 (22) ◽  
pp. 4364 ◽  
Author(s):  
Ou-Yang ◽  
Long ◽  
Du ◽  
Diao ◽  
Li

As loads connected to active distribution network (ADN) grow, ADN’s voltage safety issues are becoming more serious. At present, the solution is mainly to build more distributed generation (DG) or to adjust the reactive power in the whole network, but the former needs a lot of investment while the latter requires a large amount of communication equipment and it takes a long time to calculate the adjustment amount of reactive power and to coordinate reactive power compensation equipment. When the loads are heavy, there will still be drawbacks of insufficient reactive power. Therefore, this paper analyzes the relationship between the active power, reactive power, and the voltage in the ADN. Through the autonomous region (AR) division, a voltage control method based on the active power variation and adjustable power in the AR is proposed. According to the relationship between the amount of active power and the adjustable amount active power, the active power control, the reactive power control, and the coordinated control of active power reactive power control are adopted to adjust the DGs’ output to stabilize the bus voltage. The simulation results show that the proposed method can effectively improve the voltage control capability of ADN and can enable it to operate normally under greater power changes. Through the control method in this paper, the communication requirements are greatly reduced and the calculation time is effectively shortened and is more adaptable.


Energies ◽  
2021 ◽  
Vol 14 (4) ◽  
pp. 1121
Author(s):  
Rozmysław Mieński ◽  
Przemysław Urbanek ◽  
Irena Wasiak

The paper includes the analysis of the operation of low-voltage prosumer installation consisting of receivers and electricity sources and equipped with a 3-phase energy storage system. The aim of the storage application is the management of active power within the installation to decrease the total power exchanged with the supplying network and thus reduce energy costs borne by the prosumer. A solution for the effective implementation of the storage system is presented. Apart from the active power management performed according to the prosumer’s needs, the storage inverter provides the ancillary service of voltage regulation in the network according to the requirements of the network operator. A control strategy involving algorithms for voltage regulation without prejudice to the prosumer’s interest is described in the paper. Reactive power is used first as a control signal and if the required voltage effect cannot be reached, then the active power in the controlled phase is additionally changed and the Energy Storage System (ESS) loading is redistributed in phases in such a way that the total active power set by the prosumer program remains unchanged. The efficiency of the control strategy was tested by means of a simulation model in the PSCAD/EMTDC program. The results of the simulations are presented.


2018 ◽  
Vol 7 (2.28) ◽  
pp. 362
Author(s):  
Raed A. Shalwala

One of the most important operational requirements for any electrical power network for both distribution and transmission level is voltage control. Many studies have been carried out to improve or develop new voltage control techniques to facilitate safe connection of distributed generation. In Saudi Arabia, due to environmental, economic and development perspectives, a wide integration of photovoltaic (PV) genera-tion in distribution network is expected in the near future. This development in the network may cause voltage regulation problems due to the interaction with the existing conventional control system. In a previous paper, a control system has been described using a fuzzy logic control to set the on-line tap changer for the primary substation. In this paper a new control system is proposed for controlling the power factor of individual PV invertors based on observed correlation between net active and reactive power at each connection. A fuzzy logic control has been designed to alter the power factor for the remote invertors from the secondary substation to keep the feeder voltage within the permissible limits. In order to confirm the validity of the proposed method, simulations are carried out for a realistic distribution network with real data for load and solar radiation. Results showing the performance of the new control method are presented and discussed.  


Sign in / Sign up

Export Citation Format

Share Document