scholarly journals Energy Conservation Measures for a Research Data Center in an Academic Campus

Energies ◽  
2021 ◽  
Vol 14 (10) ◽  
pp. 2820
Author(s):  
Khaled Iyad Alsharif ◽  
Aspen Glaspell ◽  
Kyosung Choo

Simulation and experimental studies were conducted to investigate energy consumption, develop ECMs (Energy Conservation Measures), and analyze temperature increase under a power failure scenario for a research data center at Youngstown State University. Two ECMs were developed to improve energy consumption by analyzing the thermal performance of the data center: (1) increase the return temperature in air conditioning vents; (2) provide cold aisle containment with the set point temperature increase. A transient analysis was conducted under a cooling system failure scenario to predict the temperature variation over time. The results suggest that it takes 600 s to increase the server inlet temperature by 16.1 °C for the baseline model. In addition, in the ECM #2, the maximum temperature at the server inlet did not reach 40 C under the air conditioning system failure scenario, which is the maximum operating temperature of the ASHRAE A3 envelop.

Author(s):  
Kyosung Choo ◽  
Renan Manozzo Galante ◽  
Michael Ohadi

Energy Conservation Measures (ECMs) of the primary data center at the University of Maryland are developed. Measurement and simulation are performed to validate the developed ECMs. Three ECMs — 1) Increase in the return temperature at Computer Room Air Conditionings (CRACs) 2) Cold aisle containment 3) Elimination of unnecessary CRACs — are suggested to reduce energy consumption by optimizing the thermo-fluid flow in the data center. Power savings of 12.7 kW – 17.4 kW and 14.1 kW are obtained by increasing the return air temperatures at the CRACs and performing the cold aisle containment, respectively. In addition, a power saving of 11.2 kW is obtained by turning off CRACs 3 and 8 which have an adverse effect on the data center cooling.


2014 ◽  
Vol 672-674 ◽  
pp. 518-521
Author(s):  
Li Fei Song ◽  
Tao Li ◽  
Qi Fen Li ◽  
Lin Hui Zhao ◽  
Xin Zhao ◽  
...  

In this paper, the Unicom's medium-sized IDC room in a city of northern China is the research object for the study. Based on field research of the room refrigeration conditions, data center room air conditioning system is carried out to optimize and for energy conservation research. Through the analytic methods of energy saving-technology, the best energy saving solutions is explored.


Author(s):  
Mehmet Kanoglu ◽  
Ilker Karabay ◽  
Ibrahim Dincer

Efficient energy use is critical for the success of any industrial facility since reduced energy consumption through energy conservation/saving programs can benefit not only consumers and utilities, but society in general as well. In particular, reduced energy consumption generally leads to reduced emissions of greenhouse gases and other air pollutants into the environment. It also helps reduce the operational costs in the facility. There is a strong need to take some energy saving measures in every plant/ facility. Although these may be quite diverse, some of these measures include thermal insulation, use of more efficient equipment, heat recovery systems, high efficiency lighting, changing the fuel, reducing the cost of compressed air, and enhancing productivity. In this study, some certain energy conservation measures are considered for assessing a packaging film manufacturing facility in Gaziantep, Turkey. Taking advantage of dry and hot climates of the city, cooling compressor inlet air by evaporative cooling technique is also assessed. Our investigation shows that there is a huge room for energy conservation measures. The total savings potential are expected to be 869,350 YTL (about $725,000) representing about 16% of the total energy consumption. The payback periods for the identified measures are justified. We believe that the results are typical rather than exceptional for the industrial sector in Turkey.


2018 ◽  
Vol 140 (3) ◽  
Author(s):  
Heliana M. C. Aguilar ◽  
Marcos A. B. Galhardo ◽  
João T. Pinho

This paper focuses on the thermal and energetic behavior of a building located in the Brazilian Amazon Region, a region climatically characterized by elevated temperatures and high humidity levels, where achieving adequate thermal comfort demands a high-energy consumption due to the use of air-conditioning systems. Therefore, different energy conservation measures (ECMs) need to be evaluated to reduce the thermal load for cooling. The use of a thermal insulation material on the west wall and on the roof, and a photovoltaic (PV) system integrated as an architectural element and adapted to the roof of the building are considered. The building is simulated with the software energyplus, with its thermal behavior and energy consumption analyzed for an entire year and for a chosen design day, defined with data measured by a weather station installed close to the building. According to the evaluations carried out, it is determined that the ECMs have a direct and major influence on the reduction of the thermal load for cooling, on the reduction of the effects caused by radiation with the shading on the eaves, and the reduction of the transmittance on the surfaces that were modified in the study. In terms of energy consumption and economic feasibility, the ECMs reach an annual energy saving percentage of 74% for the building chosen as the case study, and the solutions adopted provide the return of the financial investment, proving suitable for energy saving and economically viable for regions with similar climatic characteristics.


Sign in / Sign up

Export Citation Format

Share Document