Abstract
To raise the maximum access ability of the maximal distributed photovoltaic system, based on the metering terminal of plant and station system for many years, a nonparametric estimation method based on kernel density is proposed to calculate harmonic probability distribution, this paper proposes the calculation method of superposition index and simultaneous coefficient suitable for distributed photovoltaic grid-connection, and puts forward the capacity calculation method considering harmonic constraints. An example shows that the proposed method can increase the maximum admittance capacity by at least 15% compared with the traditional method under the condition that the harmonic emission level does not exceed the threshold value of national standard, and realize the safe, stable and economic operation.