Investigation of the minimum ignition temperature and lower explosion limit of multi-components hybrid mixtures in the Godbert-Greenwald furnace

2017 ◽  
Vol 111 ◽  
pp. 785-794 ◽  
Author(s):  
Emmanuel Kwasi Addai ◽  
Albert Addo ◽  
Zaheer Abbas ◽  
Ulrich Krause
2016 ◽  
Vol 188 (11-12) ◽  
pp. 1693-1704 ◽  
Author(s):  
Emmanuel Kwasi Addai ◽  
Dieter Gabel ◽  
Haider Ali ◽  
Ulrich Krause

Author(s):  
Zuzana Szabová ◽  
Richard Kuracina

Abstract The article deals with the determination of fire characteristics of industrial dust samples. Particle size granulometry and determination of explosion parameters according to EN 14034 (Lower Explosion Limit LEL, Pmax, Kst) are presented. The minimum ignition temperatures of the dust layer and dispersed dust from the hot surface according to EN ISO / IEC 80079-20-2: 2016 were measured. It was found that LEL is 60 g.m−3, Pmax is 8.61 bar, and Kst is 89 bar.s−1.m. The minimum ignition temperature (MIT) of dust layer is 280 ° C and the minimum ignition temperature of dispersed dust is 400 ° C.


Fuel ◽  
2020 ◽  
Vol 264 ◽  
pp. 116811
Author(s):  
Xin Tan ◽  
Martin Schmidt ◽  
Peng Zhao ◽  
Aizhu Wei ◽  
Weixing Huang ◽  
...  

Author(s):  
Di Sha ◽  
Yucheng Li ◽  
Xihua Zhou ◽  
Ruiqing Li

Abstract The ignition and explosion of coal dust are significant hazards in coal mines. In this study, the minimum ignition temperature and energy of non-stick coal dust were investigated empirically at different working conditions to identify the key factors that influence the sensitivity and characteristics of coal dust explosions. The results showed that for a given particle size, the minimum ignition temperature of the coal dust layer was inversely related to the thickness of the coal dust layer. Meanwhile, when the layer thickness was kept constant, the minimum ignition temperature of the coal dust layer decreased with smaller coal dust particle sizes. Over the range of particle sizes tested (25–75 μm), the minimum ignition temperature of the coal dust cloud gradually increased when larger particles was used. At the same particle size, the minimum ignition temperature of the coal dust layer was much lower than that of the coal dust cloud. Furthermore, the curves of minimum ignition energy all exhibited a minimum value in response to changes to single independent variables of mass concentration, ignition delay time and powder injection pressure. The interactions of these three independent variables were also examined, and the experimental results were fitted to establish a mathematical model of the minimum ignition energy of coal dust. Empirical verification demonstrated the accuracy and practicability of the model. The results of this research can provide an experimental and theoretical basis for preventing dust explosions in coal mines to enhance the safety of production.


2018 ◽  
Vol 247 ◽  
pp. 00003
Author(s):  
Bożena Kukfisz

The paper describes the impact of adding fire extinguishing powders acting based on oxygen or flame on values of minimum ignition temperatures of the layer and cloud of pellet dust, and as a consequence the impact or lack of impact on values of maximum admissible temperature on external surfaces of electrical appliances working in their atmospheres. Tests were conducted of the minimum ignition temperature of layer and cloud of the agro armakow pellet dust and the agro jesień pellet dust, with and without additives of fire extinguishing powders BC Jet, BC LB2, ABC 90 and Ogniotex 103 at concentrations ranging from 5 to 70% by weight of powder contents in the mixture. Based on obtained test results it has been ascertained that type ABC powders appear to be much more effective than those type BC, because they have a much bigger impact on increasing the minimum ignition temperature of the layer and the cloud of analysed dust types. Adding only 15% of ABC 90 extinguishing powder to the agro jesień pellet has caused an increase in the minimum ignition temperature of dust layer by 80°C. The BC LB2 powder with agro armakow pellet dust has not been found to cause any changes, even at its concentration as high as 70%. The most optimum additive of powder to the biomass dust was 10% by weight of ABC powder in the mixture. At this concentration the highest increase was recorded in the maximum admissible temperature on the outer surface of electrical appliances from 235°C to 273°C.


2016 ◽  
Vol 36 (1) ◽  
pp. 81-94 ◽  
Author(s):  
Emmanuel Kwasi Addai ◽  
Dieter Gabel ◽  
Ulrich Krause