Power Quality Investigation of Back-to-Back Harmonic Filters for a High-Voltage Anode Foil Manufacturing Facility

Author(s):  
Thomas J. Dionise ◽  
Visuth Lorch ◽  
Brandon J. Brazil
2018 ◽  
Vol 1 (1) ◽  
pp. 54-66
Author(s):  
Rakan Khalil Antar ◽  
Basil Mohammed Saied ◽  
Rafid Ahmed Khalil

A new control strategy for active power filters is proposed, modeled and implemented in order to improve the power quality of a line commutated converter High voltage DC link. The ability of reactive power and harmonics reductions are generally met by using passive and active power filters. In this paper, modified active power filter with a modified harmonics pulse width modulation algorithm is used to minimize the source harmonics and force the AC supply current to be in the same phase with AC voltage source at both sending and receiving sides of a line commutated converter high voltage DC link. Therefore, it is considered as power factor corrector and harmonics eliminator with random variations in the load current. The modified harmonics pulse width modulation algorithm is applicable for active power filter based on a three-phase five-level and seven-level cascaded H-bridge voltage source inverter. Simulation results show that the suggested modified multilevel active power filters improve total harmonics distortion of both voltage and current with almost unity effective power factor at both AC sides of high voltage DC link. Therefore, modified active power filter is an effective tool for power quality improvement and preferable for line commutated converter high voltage DC link at different load conditions.


Author(s):  
Yen-Ming Tseng ◽  
Hsi-Shan Huang ◽  
Chen JiQuan ◽  
Wang Xuefei ◽  
Chen Han ◽  
...  

According to IEEE-1159 definition and classification of power quality of applying at supplyside and demand-side of power system to evaluate the power quality of high voltage keycustomer and using the voltage events record (VER) in low voltage level supply. Which voltage parameter set of VER with specific software Event View software by Fluke and can collect event data, plot graphic of event data sets that can using the data mining skill to analysis the voltage swell, voltage sag, power outage, frequency events and three phase load unbalance of high voltage key-customer. By abnormal voltage event statistics with discriminated by quantization of high voltage key-customer which can evaluate the own power quality and an also provide reference for quality requirements for related semiconductor factories with higher demand that can avoid the significant effect the economic losses.


Energies ◽  
2019 ◽  
Vol 12 (10) ◽  
pp. 2021 ◽  
Author(s):  
Yuehui Chen ◽  
Zhao Huang ◽  
Zhenfeng Duan ◽  
Pengwu Fu ◽  
Guandong Zhou ◽  
...  

This paper solves the problem of reactive power and harmonics compensation in a high-voltage (HV) distribution network supplying nonlinear loads. An inductive filtering (IF) approach where passive filters connect to the filtering winding of a four-winding inductive filtering transformer (FW-IFT) is presented to enhance the power quality of the public grid. This method can not only greatly suppress harmonic currents of the medium and/or low-voltage (LV) side, but also prevent them from flowing into the public grid. The new main circuit topology, where the FW-IFT has specific filtering winding by adopting the ampere-turn balance of the transformer, is presented. On the basis of the structure of the FW-IFT, the magnetic potential balanced equation and inductive filtering technology, its equivalent circuit and mathematical model are established, and the filtering performances are analyzed in detail. Simulation and experimental results rated at SN-10/0.38 of the FW-IFT are presented to prove the efficacy of the comprehensive enhancement of power quality on the grid side.


2016 ◽  
Vol 31 (12) ◽  
pp. 8182-8194 ◽  
Author(s):  
Qianming Xu ◽  
Fujun Ma ◽  
An Luo ◽  
Zhixing He ◽  
Huagen Xiao