Vapor-Venting, Micromachined Heat Exchanger for Electronics Cooling

Author(s):  
Milnes P. David ◽  
Tarun Khurana ◽  
Carlos Hidrovo ◽  
Beth L. Pruitt ◽  
Kenneth E. Goodson

The increasing complexity of modern integrated circuits and need for high-heat flux removal with low junction temperatures motivates research in a wide variety of cooling and refrigeration technologies. Two-phase liquid cooling is especially attractive due to high efficiency and low thermal resistances. While two-phase microfluidic cooling offers important benefits in required flow rate and pump size, there are substantial challenges related to flow stability and effective superheating. This work investigates the use of hydrophobic membrane to locally vent the vapor phase in microfluidic heat exchangers. Previous work has demonstrated selective venting of gas in microstructures and we extend this concept to two-phase heat exchangers. This paper details the design, fabrication and preliminary testing of the novel heat exchanger. Proof-of-concept of the device, carried out using an isothermal air-water mixture, found the air-mass venting efficiency exceeding 95%. Two-phase, thermal operation of the heat exchanger found the pressure-drop to be smaller compared to a two-phase, non-venting model. The paper also includes a discussion of design challenges such as membrane leakage and optical inaccessibility. The favorable results demonstrated in this first-generation, vapor-venting, micromachined, heat exchanger motivates further study of this and other novel microstructures aimed at mitigating the negative effects of phase-change. With continued research and optimization, we believe two-phase cooling is a viable solution for high heat flux generating electronics.

Author(s):  
Farhad Saffaraval ◽  
Amir Jokar

The objective of this study is to experimentally explore thermodynamic performance of R245fa, as a low-pressure and environmentally-friendly refrigerant, in a microchannel heat exchanger. This heat exchanger is used in an electronics cooling application with high-power density. Due to the large amount of latent heat that is released during evaporation process, the two-phase microchannel coolers are able to remove much more energy compared to single-phase cooling systems. In this study, R245fa is used as the working fluid in a refrigeration pump loop that mainly includes an evaporator, a condenser, a refrigerant pump, and a pressure regulator valve. The goal is to obtain optimal mass flow rates and system pressures while the temperatures in evaporator and condenser are kept constant for specific conditions. The results obtained from this study are then compared to the results previously obtained for water as the working fluid in a similar cooling system. It is expected the evaporative cooling through the microchannel heat exchanger be a viable and effective solution, especially for higher heat flux applications.


Author(s):  
Oyuna Angatkina ◽  
Andrew Alleyne

Two-phase cooling systems provide a viable technology for high–heat flux rejection in electronic systems. They provide high cooling capacity and uniform surface temperature. However, a major restriction of their application is the critical heat flux condition (CHF). This work presents model predictive control (MPC) design for CHF avoidance in two-phase pump driven cooling systems. The system under study includes multiple microchannel heat exchangers in series. The MPC controller performance is compared to the performance of a baseline PI controller. Simulation results show that while both controllers are able to maintain the two-phase cooling system below CHF, MPC has significant reduction in power consumption compared to the baseline controller.


Author(s):  
David C. Deisenroth ◽  
Avram Bar-Cohen ◽  
Michael Ohadi

Two-phase cooling has become an increasingly attractive option for thermal management of high-heat flux electronics. Cooling channels embedded directly on the back of the heat source (chip) facilitate two-phase boiling/evaporation effectiveness, eliminating many thermal resistances generated by more traditional, remote chip-cooling approaches. Accordingly, manifold-microchannel flow paths in embedded cooling systems can allow very high heat fluxes with low junction temperatures. But, the effect of the feeding manifold design, channel geometry, and the associated shear, stagnation zones, and centripetal accelerations with varying heat flux and mass flux are not well understood. This study builds upon our previous work and elucidates effects of channel geometry, mass flux, and outlet quality on the boiling/evaporation flow regimes in a manifolded microgap channel.


Author(s):  
Harsh Tamakuwala ◽  
Ryan Von Ness ◽  
Debjyoti Banerjee

Plate-fin heat exchangers are widely used in industries especially aerospace, cryogenics, food and chemical process industries where high heat flux surface area per unit volume is of prime importance. These heat exchangers consists of series of corrugated plates (herringbone or chevron), separated by gasket sealing. Chevron angled plates are one of the most commonly used type of geometry. The complex design of chevron plate heat exchanger, induces high turbulence and flow reversals causing high heat transfer through the plates. This paper discusses about the computational fluid dynamics simulations conducted over a simplified geometry of Chevron Plate Heat Exchanger to understand the formulation of vortices at different Reynold’s number for various aspect ratios. A single phase laminar flow with periodic boundary condition is used for analysis of the fluid behavior in a unit pattern of the corrugation geometry. Based on different flow and geometric conditions, varying amounts of swirl-flows are observed and different behavior of shear stress and heat transfer plot along the length of the plate is observed. At higher Reynolds numbers (Re), the re-circulations and mixing by the induced vortices causes significant rise of heat flux, with marginal increase in friction factor.


2008 ◽  
Vol 130 (7) ◽  
Author(s):  
Yiding Cao ◽  
Mingcong Gao

This paper conducts experimental and analytical studies of a novel heat-transfer device, reciprocating-mechanism driven heat loop (RMDHL) that facilitates two-phase heat transfer while eliminating the so-called cavitation problem commonly encountered by a conventional pump. A RMDHL normally includes a hollow loop having an interior flow passage, an amount of working fluid filled within the loop, and a reciprocating driver. The hollow loop has an evaporator section, a condenser section, and a liquid reservoir. The reciprocating driver is integrated with the liquid reservoir and facilitates a reciprocating flow of the working fluid within the loop, so that liquid is supplied from the condenser section to the evaporator section under a substantially saturated condition and the so-called cavitation problem associated with a conventional pump is avoided. The reciprocating driver could be a solenoid-operated reciprocating driver for electronics cooling applications and a bellows-type reciprocating driver for high-temperature applications. Experimental study has been undertaken for a solenoid-operated heat loop in connection with high heat flux thermal management applications. Experimental results show that the heat loop worked very effectively and a heat flux as high as 300W∕cm2 in the evaporator section could be handled. A working criterion has also been derived, which could provide a guidance for the design of a RMDHL.


Author(s):  
Rongliang Zhou ◽  
Juan Catano ◽  
Tiejun Zhang ◽  
John T. Wen ◽  
Greg J. Michna ◽  
...  

Steady-state modeling and analysis of a two-loop cooling system for high heat flux removal applications are studied. The system structure proposed consists of a primary pumped loop and a vapor compression cycle (VCC) as the secondary loop to which the pumped loop rejects heat. The pumped loop consists of evaporator, condenser, pump, and bladder liquid accumulator. The pumped loop evaporator has direct contact with the heat generating device and CHF must be higher than the imposed heat fluxes to prevent device burnout. The bladder liquid accumulator adjusts the pumped loop pressure level and, hence, the subcooling of the refrigerant to avoid pump cavitation and to achieve high critical heat flux (CHF) in the pumped loop evaporator. The vapor compression cycle of the two-loop cooling system consists of evaporator, liquid accumulator, compressor, condenser and electronic expansion valve. It is coupled with the pumped loop through a fluid-to-fluid heat exchanger that serves as both the vapor compression cycle evaporator and the pumped loop condenser. The liquid accumulator of the vapor compression cycle regulates the cycle active refrigerant charge and provides saturated vapor to the compressor at steady state. The heat exchangers are modeled with the mass, momentum, and energy balance equations. Due to the projected incorporation of microchannels in the pumped loop to enhance the heat transfer in heat sinks, the momentum equation, rarely seen in previous refrigeration system modeling efforts, is included to capture the expected significant microchannel pressure drop witnessed in previous experimental investigations. Electronic expansion valve, compressor, pump, and liquid accumulators are modeled as static components due to their much faster dynamics compared with heat exchangers. The steady-state model can be used for static system design that includes determining the total refrigerant charge in the vapor compression cycle and the pumped loop to accommodate the varying heat load, sizing of various components, and parametric studies to optimize the operating conditions for a given heat load. The effect of pumped loop pressure level, heat exchangers geometries, pumped loop refrigerant selection, and placement of the pump (upstream or downstream of the evaporator) are studied. The two-loop cooling system structure shows both improved coefficient of performance (COP) and CHF overthe single loop vapor compression cycle investigated earlier by authors for high heat flux removal.