scholarly journals Evaporative cooling of an atomic beam

2000 ◽  
Vol 10 (1) ◽  
pp. 9-18 ◽  
Author(s):  
E. Mandonnet ◽  
A. Minguzzi ◽  
R. Dum ◽  
I. Carusotto ◽  
Y. Castin ◽  
...  
2005 ◽  
Vol 72 (3) ◽  
Author(s):  
T. Lahaye ◽  
Z. Wang ◽  
G. Reinaudi ◽  
S. P. Rath ◽  
J. Dalibard ◽  
...  

2006 ◽  
Vol 73 (6) ◽  
Author(s):  
Thierry Lahaye ◽  
David Guéry-Odelin

2013 ◽  
Vol 44 (1) ◽  
pp. 39-54
Author(s):  
A. Wehlmann ◽  
W. Hater ◽  
F. Wolf ◽  
R. Lunkenheimer ◽  
C. Foret ◽  
...  

Energies ◽  
2020 ◽  
Vol 13 (12) ◽  
pp. 3061 ◽  
Author(s):  
Shazia Noor ◽  
Hadeed Ashraf ◽  
Muhammad Sultan ◽  
Zahid Mahmood Khan

This study provides comprehensive details of evaporative cooling options for building air-conditioning (AC) in Multan (Pakistan). Standalone evaporative cooling and standalone vapor compression AC (VCAC) systems are commonly used in Pakistan. Therefore, seven AC system configurations comprising of direct evaporative cooling (DEC), indirect evaporative cooling (IEC), VCAC, and their possible combinations, are explored for the climatic conditions of Multan. The study aims to explore the optimum AC system configuration for the building AC from the viewpoints of cooling capacity, system performance, energy consumption, and CO2 emissions. A simulation model was designed in DesignBuilder and simulated using EnergyPlus in order to optimize the applicability of the proposed systems. The standalone VCAC and hybrid IEC-VCAC & IEC-DEC-VCAC system configurations could achieve the desired human thermal comfort. The standalone DEC resulted in a maximum COP of 4.5, whereas, it was 2.1 in case of the hybrid IEC-DEC-VCAC system. The hybrid IEC-DEC-VCAC system achieved maximum temperature gradient (21 °C) and relatively less CO2 emissions as compared to standalone VCAC. In addition, it provided maximum cooling capacity (184 kW for work input of 100 kW), which is 85% higher than the standalone DEC system. Furthermore, it achieved neutral to slightly cool human thermal comfort i.e., 0 to −1 predicted mean vote and 30% of predicted percentage dissatisfied. Thus, the study concludes the hybrid IEC-DEC-VCAC as an optimum configuration for building AC in Multan.


Sign in / Sign up

Export Citation Format

Share Document