scholarly journals Research on additional damping control of sub-synchronous oscillation in series-compensated DFIG system

2021 ◽  
Vol 2087 (1) ◽  
pp. 012053
Author(s):  
Weili Liang ◽  
Jiguang Wu

Abstract Since series-compensated grid-connected system of doubly fed induction generator (DFIG) may cause sub-synchronous oscillation, with the purpose of improving the system stability, in this paper, the mechanism of sub-synchronous oscillation (SSO) is analyzed from the perspective of system damping, according to the mechanism, an additional damping controller is designed to suppress SSO. The controller uses rotor speed as the input signal and adds it into the d-axis current inner loop of the grid-side converter through filtering and proportional amplification, with the purpose of providing positive damping to the system. Finally, the model of DFIG series-compensated grid-connected system is established on PSCAD/EMTDC simulation platform to verify the suppression effect of the additional damping controller through time-domain simulation. The simulation results show that the device has good respond speed and suppression effect.

Author(s):  
Ihedrane Yasmine ◽  
El Bekkali Chakib ◽  
Bossoufi Badre

<span lang="EN-US">The following article presents the control of the power generated by the Doubly Fed Induction Generator, integrated into the wind system, whose rotor is linked to the power converters (Rotor Side Convert (RSC) and Grid Side Converter (GSC)) interfaced by the DC-BUS and connected to the grid via a filter (Rf, Lf) in order to obtain an optimal power to the grid and to ensure system stability. The objective of this study is to understand and to make the comparison between Sliding mode Control technique and the Flux Oriented Control in order to control the Doubly Fed Induction Generator powers exchanged with the grid, it also aims at maintaining the DC-BUS voltage constant and a unit power factor at the grid connection point.The results of simulation show the performance of the Sliding mode Control in terms of monitoring, and robustness with regard to the parametric variations, compared to the Flux Oriented Control. The performance of the systems was tested and compared with the use of MATLAB/Simulink software.</span>


2021 ◽  
Vol 233 ◽  
pp. 01025
Author(s):  
Yingfeng Zhu ◽  
Xiaosu Xie ◽  
Dong Yang ◽  
Song Gao ◽  
Weichao Zhang ◽  
...  

Doubly fed induction generator (DFIG) wind power generation system is widely used in wind farm all over the world. Reactive power can be generated both in grid-side converter and generator-side converter of DFIG. In this paper, working principle and control method of DFIG are introduced, and the reactive power limit of DFIG is derived, finally reactive power regulation is simulated in Simulink.


2012 ◽  
Vol 538-541 ◽  
pp. 3125-3128
Author(s):  
Wei Zhang ◽  
Yi Ruan

A mathematic model of the grid-side PWM converter based on Doubly-Fed Induction Generator (DFIG) has been investigated to analyze their operating characteristics. The control scheme to the grid-side PWM converter was presented. And the simulation model of the grid-side converter (GSC) based on DFIG energy generation system was built in Matlab / simulink software. The results show the feasibility and correctness of the control strategy.


Energies ◽  
2021 ◽  
Vol 14 (22) ◽  
pp. 7685
Author(s):  
Xiangwu Yan ◽  
Wenfei Chang ◽  
Sen Cui ◽  
Aazim Rassol ◽  
Jiaoxin Jia ◽  
...  

A large-scale power system breakdown in the United Kingdom caused blackouts in several important cities, losing about 3.2 percent of the load and affecting nearly 1 million power users on 9 August 2019. On the basis of the accident investigation report provided by the UK National Grid, the specific reasons for the sub-synchronous oscillation of Hornsea wind farm were analyzed. The Hornsea wind power system model was established by MATLAB simulation software to reproduce the accident. To solve this problem, based on the positive and negative sequence decomposition, the control strategy of grid-side converter of doubly-fed induction generator is improved to control the positive sequence voltage of the generator terminal, which can quickly recover the voltage by compensating the reactive power at the grid side. Consequently, the influence of the fault is weakened on the Hornsea wind farm system, and the sub-synchronous oscillation of the system is suppressed. The simulation results verify the effectiveness of the proposed control strategy in suppressing the sub-synchronous oscillation of weak AC wind power system after being applied to doubly-fed induction generator, which serves as a reference for studying similar problems of offshore wind power.


Sign in / Sign up

Export Citation Format

Share Document