Analysis of Dynamic Arc Parameters for Vacuum Circuit Breaker under Short-circuit Current Breaking

Author(s):  
Hai Chen ◽  
Xiaoming Liu ◽  
Longnv Li ◽  
Yixiong Liu ◽  
Yaqian Zhang ◽  
...  
2019 ◽  
Vol 29 (2) ◽  
pp. 1-5 ◽  
Author(s):  
Hai Chen ◽  
Xiaoming Liu ◽  
Longnv Li ◽  
Yixiong Liu ◽  
Yaqian Zhang ◽  
...  

2012 ◽  
Vol 614-615 ◽  
pp. 1138-1141 ◽  
Author(s):  
Peng Sun ◽  
Cong Jun Xue

The Axial Magnetic Field (AMF) applied to the arc vacuum column in the vacuum tube can make the vacuum arc keeping in diffusion state, provided that the short circuit current to be interrupt is within a critical value. In the results, the breaking ability of Vacuum Interrupters can be highly improved with the help of the AMF. The experimental study has proved that the AMF should be sufficient strong and have optimum distribution, in order to improve the breaking capacity of vacuum circuit breaker. This paper presents a novel axial magnetic contact with the concave axial magnetic field distribution and its 3-d simulation.


Energies ◽  
2021 ◽  
Vol 14 (14) ◽  
pp. 4285
Author(s):  
Kui Ma ◽  
Xiaofei Yao ◽  
Luyang Zhang ◽  
Shaogui Ai ◽  
Shuhong Wang ◽  
...  

It is effective to open the bus-coupler circuit breaker in case of a short-circuit fault. A fast vacuum circuit breaker (FVCB) is an ideal bus-coupler circuit breaker due to its high velocity. The objective of this study was to develop and test a 252 kV/2500 A-40 kA multi-break bus-coupler FVCB. The 252 kV FVCB contained 12 FVCB units. Each phase consisted of four FVCB units connected in series. Each FVCB unit had an electromagnetic repulsion mechanism with an average opening velocity reaching 6.5 m/s. Test results showed the opening time was 1.11 ± 0.08 ms. The capacitance of the voltage grading capacitor of each break was determined to be 10 nF. The prototype 252 kV bus-coupler FVCB passed all partial test duties according to the IEC 62271-100: 2008 and IEC 62271-1: 2007 standards, which include an insulation test and a terminal fault test among others. A 252 kV/2500 A-40 kA multi-break bus-coupler FVCB can be used to quickly cut off a short-circuit fault and effectively limit a short-circuit current.


Author(s):  
Chen Guan ◽  
Xiaofei Yao ◽  
Weidong Wang ◽  
Ran Zhang ◽  
Luyang Zhang ◽  
...  

2021 ◽  
Vol 39 (5A) ◽  
pp. 723-737
Author(s):  
Yamur M. Obied ◽  
Thamir M. Abdul Wahhab

The coordination between protective devices is the process of determining the most appropriate timing of power interruption during abnormal conditions in the power system. The aim of this work is to coordinate the protection of the 33/11 kV power distribution substation in Iraq using the CYME 7.1 software package. In this paper overcurrent and earth fault relays are simulated in two cases, with time delay setting and instantaneous setting, to obtain the Time Current Characteristics (TCC) curves for each Circuit Breaker (CB) relay of Al-Karama substation (2×31.5 MVA, 33/11 kV) in Babil distribution network. The short circuit current at each CB is calculated and accordingly, the protection coordination for Al-Karama substation has been simulated. The TCC curves have been obtained in two cases for overcurrent and earth fault relays; in a case with time delay setting and in the case with the instantaneous setting. The setting takes into consideration the short circuit current at the furthest point of the longest outgoing feeder and the shortest outgoing feeder.


Energies ◽  
2019 ◽  
Vol 12 (13) ◽  
pp. 2512 ◽  
Author(s):  
Xiao Yu ◽  
Fan Yang ◽  
Xing Li ◽  
Shaogui Ai ◽  
Yongning Huang ◽  
...  

A balanced voltage distribution for each break is required for normal operation of a multi-break vacuum circuit breaker (VCB) This paper presented a novel 363 kV/5000 A/63 kA sextuple-break VCB with a series-parallel structure. To determine the static voltage distribution of each break, a 3D finite element method (FEM) model was established to calculate the voltage distribution and the electric field of each break at the fully open state. Our results showed that the applied voltage was unevenly distributed at each break, and that the first break shared the most voltage, about 86.3%. The maximum electric field of the first break was 18.9 kV/mm, which contributed to the reduction of the breaking capacity. The distributed and stray capacitance parameters of the proposed structure were calculated based on the FEM model. According to the distributed capacitance parameters, the equivalent circuit simulation model of the static voltage distribution of this 363 kV VCB was established in PSCAD. Subsequently, the influence of the grading capacitor on the voltage distribution of each break was investigated, and the best value of the grading capacitors for the 363 kV sextuple-break VCB was confirmed to be 10 nF. Finally, the breaking tests of a single-phase unit was conducted both in a minor loop and a major loop. The 363 kV VCB prototype broke both the 63 kA and the 80 kA short circuit currents successfully, which confirmed the validity of the voltage sharing design.


Energies ◽  
2020 ◽  
Vol 13 (2) ◽  
pp. 334
Author(s):  
Esteban Pulido ◽  
Luis Morán ◽  
Felipe Villarroel ◽  
José Silva

In this paper, a new concept of short-circuit current (SCC) reduction for power distribution systems is presented and analyzed. Conventional fault current limiters (FCLs) are connected in series with a circuit breaker (CB) that is required to limit the short-circuit current. Instead, the proposed scheme consisted of the parallel connection of a current-controlled power converter to the same bus intended to reduce the amplitude of the short-circuit current. This power converter was controlled to absorb a percentage of the short-circuit current from the bus to reduce the amplitude of the short-circuit current. The proposed active short-circuit current reduction scheme was implemented with a cascaded H-bridge power converter and tested by simulation in a 13.2 kV industrial power distribution system for three-phase faults, showing the effectiveness of the short-circuit current attenuation in reducing the maximum current requirement in all circuit breakers connected to the same bus. The paper also presents the design characteristics of the power converter and its associated control scheme.


Electronics ◽  
2020 ◽  
Vol 9 (2) ◽  
pp. 306 ◽  
Author(s):  
Lujun Wang ◽  
Boyu Feng ◽  
Yu Wang ◽  
Tiezhou Wu ◽  
Huipin Lin

In order to solve the imminent problem in that the traditional protection strategy cannot meet time requirements, together with the fact that the rotational inertia of a DC microgrid is small and short-circuit fault develops rapidly, a bidirectional short-circuit current blocker (BSCCB) based on solid-state circuit breaker for a DC microgrid is proposed. Firstly, the bidirectional current blocking circuit structure is proposed based on the analysis of key components. Then, a top-level differential protection strategy is developed based on the aforementioned proposal. Finally, the performance of the blocking circuit is simulated and verified by experiments. The results show that the proposed method can block short-circuit current within 4 ms, and the response speed of the protection strategy is very fast compared with previous approaches. BSCCB also has reclosing, bidirectional blocking and energy releasing functions. The current blocker proposed in this paper can be reused multiple times and has a promising future in low-voltage DC microgrid application.