Structural design and seismic qualification of extra high voltage disconnect switch

1986 ◽  
Vol 13 (4) ◽  
pp. 485-497
Author(s):  
R. Kar

This paper describes the structural design approach and the method of seismic qualification for an extra high voltage disconnect switch, a vital component in the substations of a power system network. Shaping and sizing of porcelain members of the frame received special attention to enhance their resistance to earthquake. A carefully developed finite element model, on analysis by response spectrum and time-history methods, showed acceptable seismic performance and an adequate margin of safety. Shake table tests for seismic qualification, called for by the specification, were not feasible owing to the large dimensions of the complete assembly. The alternative approach was to perform in situ modal tests. By exciting the structure with a random force through a portable hydraulic exciter and using accelerometers to record the structural response, the dynamic characteristics of the equipment — the frequencies, mode shapes, and damping — were determined. Correlation between the results of finite element analysis and experimental modal analysis confirmed the validity of the analytical model. Application of combined analysis and testing for seismic qualification is demonstrated by a case study on an 800 kV disconnect switch.

2013 ◽  
Vol 284-287 ◽  
pp. 1831-1835
Author(s):  
Wei Hsin Gau ◽  
Kun Nan Chen ◽  
Yunn Lin Hwang

In this paper, two experimental techniques, Electronic Speckle Pattern Interferometry and Stroboscopic Interferometry, and two different finite element analysis packages are used to measure or to analyze the frequencies and mode shapes of a micromachined, cross-shaped torsion structure. Four sets of modal data are compared and shown having a significant discrepancy in their frequency values, although their mode shapes are quite consistent. Inconsistency in the frequency results due to erroneous inputs of geometrical and material parameters to the finite element analysis can be salvaged by applying the finite element model updating procedure. Two updating cases show that the optimization sequences converge quickly and significant improvements in frequency prediction are achieved. With the inclusion of the thickness parameter, the second case yields a maximum of under 0.4% in frequency difference, and all parameters attain more reliable updated values.


2019 ◽  
Vol 118 ◽  
pp. 02039
Author(s):  
Jin Xiao ◽  
Mingduo Huang ◽  
Qiguo Sun

The finite element model of suspended converter valve in an UHVDC transmission project with characteristics of flexible is constructed, and its vibration characteristics are simulated and analyzed firstly. The results show that this kind of suspended converter valve has obvious long-period character. Secondly, the long period phase of standard response spectrum in Code for Seismic Design of Buildings (GB50011-2010) is modified, and then the artificial seismic wave is synthesized employing the triangular series method. The result shows that this artificial seismic wave has long-period character. Finally, the time-history seismic dynamic simulation of the converter valve is done, and the seismic responses of the converter valve excited by three kinds of seismic wave with different period characters are compared and analyzed. The results show that the swing and stress of the suspended converter valve are larger under the long-period seismic wave synthesized in this paper. The quasi-resonance damage caused by long-period seismic wave should be concerned specially in the actual UHVDC transmission project.


2013 ◽  
Vol 663 ◽  
pp. 80-86
Author(s):  
Hai Qing Liu ◽  
Ming Ji Ma ◽  
Gui Jun Wang

More and more irregular structure appears in people's lives, while the theoretical research and disaster experience show that the irregular structure in the earthquake will produce translation and torsion coupled spatial vibration, and sometimes it will cause very serious consequences. Being based on the practical engineering -the Castle Hotel of Dalian, this text makes use of finite element analysis software--- ANSYS. By analyzing the dynamic characteristics and seismic response, we get the self-vibration characteristics of the structure and the time history curve of top level displacement and acceleration of the structure under the effect of earthquake forces. The calculation results indicate that it is effective and reasonable to set up three-dimensional finite element model used for the analyzing of seismic response by ANSYS.


2011 ◽  
Vol 411 ◽  
pp. 54-58
Author(s):  
Tao Feng ◽  
Xiao Li Jin

Based on the analytical theories of the joint surface, finite element modeling method of two kinds of joint about rails and bolts were studied. The finite element model of the engraving machine is built and its static and dynamic characterization is analyzed by the universal ANSYS. By this way, unreasonable structural design of engraving machine can be conducted, which will provide support for the optimization design of the structure. The correctness of the modeling method of joint surface is confirmed.


2011 ◽  
Vol 199-200 ◽  
pp. 1126-1129
Author(s):  
Su Fang Fu ◽  
Han Gao ◽  
Jia Xi Du ◽  
Qiu Ju Zhang ◽  
Xue Ming Zhang ◽  
...  

In this paper, the finite element model for the cabinet of a drum washing machine and the model for testing vibration of the cabinet were developed in ANSYS software and PULSE™, respectively. A series of tests were conducted. The natural frequencies and mode shapes were obtained by finite element analysis and modal experiment, which revealed weak parts of the cabinet. Meanwhile, the computational modes were in good agreement with experimental ones and this could provide an available method by which it was convenient to improve the design of the cabinet.


2010 ◽  
Vol 145 ◽  
pp. 317-320
Author(s):  
Chun Ming Zhang ◽  
Run Yuan Hao

This text is on the basis of the investigation of the 42MN flatting mill’s higher beam, establishing the flatting mill’s higher beam’s finite element model and the mathematical model which has optimum structure. According to the results of their structure finite element analysis, weaved the relevant procedures and optimized them, obtained ideal structural parameters, this text provide better ideas and ways for the structural design of the flatting mill’s higher beam.


Author(s):  
Budy Notohardjono ◽  
Richard Ecker ◽  
Shawn Canfield

A mainframe computer’s structure consists of a frame or rack, drawers with central processor units, IO equipment, memory and other electronic equipment. The focus of this structural mechanical analysis and design is on the frame, earthquake stiffening brackets and tie-down methods. The primary function of the frame is to protect critical electronic equipment in two modes. The first mode is during shipping shock and vibration, which provides excitation primarily in the vertical direction. The second mode of protection is protecting the equipment during seismic events where horizontal vibration can be significant. Frame stiffening brackets and tie-downs are features added to mainframe systems that must meet earthquake resistance requirements. Designing to withstand seismic events requires significant analysis and test efforts since the functional performance of the system must be maintained during and after seismic events. The frame stiffening brackets and anchorage system must have adequate strength and stiffness to counteract earthquake-induced forces, thereby preventing human injury and potential system damage. The frame’s stiffening bracket and tie-down combination must ensure continued system operation by limiting overall displacement of the structure to acceptable levels, while not inducing undue stress to the critical electronic components. This paper discusses the process of finite element analysis and testing of a mainframe computer structure to develop a design that can withstand a severe earthquake test profile. Finite element analysis modeling tools such as ANSYS, a general-purpose finite element solver, was used to analyze the initial frame design CAD model. Both implicit and explicit finite element methods were used to analyze the mainframe subjected to uniaxial and triaxial earthquake test profiles. The seismic simulation tests involve extensive uniaxial and triaxial earthquake testing in both raised floor and non-raised floor environments at a test facility. Prior to this extensive final test, in-house tests were conducted along with modal analysis of the prototype frame hardware. These tests are used to refine the dynamic characteristics of the finite element model and to design the frame stiffening bracket and tie-down system. The purpose of the modeling and in-house testing is to have a verified finite element model of the server frame and components, which will then lead to successful, seismic system tests. During experimental verification, the dynamic responses were recorded and analyzed in both the time and frequency domains. The use of explicit finite element modeling, specifically LS-DYNA, extends the capability of implicit, linear modeling by allowing the incorporation of test data time history input and the experimentally derived damping ratio. When combined with the ability to model non-linear connections and material properties, this method provides better correlation to measured test results. In practice, the triaxial seismic time history was applied as input to the finite element model, which predicted regions of plastic strain and deformation. These results were used to iteratively simulate enhancements and successfully reduce structural failure in subsequent testing.


Author(s):  
Yao Di ◽  
Cai Lijian ◽  
Meng Jian ◽  
Zhao Jintao

Based on the basic principle of fluid-structure interaction, this paper make a finite element analysis of seismic on upper water tank of HPR1000 outer containment by CEL method in ABAQUS software. Firstly, structure is simulated the by Lagrange grid and the water in upper water tank by Eulerian grid; secondly, coupling contact between water and structure is defined; finally, the calculation results are got by running an explicit dynamic solver to makes a time history analysis of fluid-structure interaction finite element model under the seismic, and the results will be used in the structure design of outer containment and upper water tank.


2014 ◽  
Vol 501-504 ◽  
pp. 1493-1497
Author(s):  
Shu He Wang ◽  
Ji Yuan ◽  
Rui Guo Ma ◽  
Ju Bing Zhang

According to No.3 dam section of Dahuaqiao gravity dam, a three-dimensional finite element model is built by finite element software ANSYS. Mechanics of materials method, response spectrum method and time history analysis method are employed to analyze the strength of the dam section. Results show that the stress of dam toe, dam heel and downstream fold slope are relatively high and stress concentration emerges in those positions. The phenomenon indicates that these areas are vulnerable under the earthquake and precautions must be taken. But under the designed earthquake, the maximum stress of the dam section is below the allowable stress, representing the dam is in a safe state and the strength requirement is satisfied.


2016 ◽  
Vol 2016 ◽  
pp. 1-12 ◽  
Author(s):  
Anxin Guo ◽  
Huixing Gao

This paper investigates the seismic performance of posttensioned concrete piers with external viscoelastic dampers to improve the energy dissipation capacity of this type of structure. An installation scheme for viscoelastic dampers on bridge piers is proposed, and the mechanical models of the damper are analyzed according to the installation scheme. By attaching the viscoelastic dampers to the posttensioned bridge piers, the analytical model of the hybrid system is established using the OpenSees finite element analysis package. Cyclic behavior and time history analyses are conducted on a posttensioned bridge with and without viscoelastic dampers using the established finite element model. The analysis results indicate that the viscoelastic dampers can effectively improve the seismic performance of the bridge structures with posttensioned piers.


Sign in / Sign up

Export Citation Format

Share Document