scholarly journals Arcing Behaviors in the Large-capacity HV SF6 Gas-blast Interrupters

2019 ◽  
Vol 6 (2) ◽  
pp. 140-143 ◽  
Author(s):  
S. A. Averyanova ◽  
E. Tonkonogov

A comprehension of the dielectric strength recovery processes during the interruption of short-circuit currents in the high-voltage SF<sub>6</sub> gas-blast circuit breakers is necessary for their modernisation in order to increase the rated voltage and short circuit breaking current per one break. This paper presents numerical results of the turbulence effects on the interruption ability in the SF<sub>6</sub> extinguishing arc chamber.

2016 ◽  
Vol 63 (0) ◽  
pp. 43-60 ◽  
Author(s):  
Janusz BANDEL ◽  
Artur HEJDUK ◽  
Andrzej DZIERŻYŃSKI ◽  
Piotr KORYCKI ◽  
Henryk SIBILSKI

This paper deals with the surges generated in the network during switching operations and lightning surges. The level of both kinds of surge was compared with the required dielectric strength between the open contacts of 245 kV circuit breakers. Overvoltages greater than the electrical withstand voltage of the circuit breaker can cause arc ignition between the circuit breaker’s open contacts and power engineering service s have reported such cases. The results of such failures can be very serious. This is a problem especially for single-break circuit breakers, in which the stresses on the electrical insulation between the open contacts of the breaker are very high. A method for selecting lightning arresters to lower the overvoltages is proposed. The switching of short-circuit currents by a circuit breaker may cause a weakening of the circuit breaker chamber’s insulation and reduce its electrical withstand and durability.


2019 ◽  
Vol 6 (2) ◽  
pp. 170-174
Author(s):  
N. Wenzel ◽  
W. Haas

The post-arc (PA) characteristics of vacuum arcs in transverse magnetic field contacts are studied for short-circuit currents of up to 123 kA peak and transient recovery voltages below 875 V. The measured PA currents are interpreted in terms of an Electric Resistance Model and the models of Andrews-Varey, Langmuir-Child, and Slepian-Schmelzle. Whereas in the late PA period, the calculations do not agree well with the measurements, the PA behavior is well described in the early period after current-zero. It is concluded that the PA discharge is amplified by ionization of metal vapor particles in the boundary sheath due to electron impact.


2020 ◽  
Vol 220 ◽  
pp. 01011
Author(s):  
Igor Nikolaevich Fomin ◽  
Roman Pavlovich Belikov ◽  
Tatyana Anatolyevna Kudinova ◽  
Nailya Kamilevna Miftakhova

Circuit breakers with automatic transfer switches (ATS) are designed in such a way that when the voltage disappears during a short-circuit (SC) in the ring network line, the ATS device is triggered. At the same time, its switch is turned on at short-circuit, then it is turned off with acceleration. Even a shortterm switching on of the automatic transfer switch for a sustained short-circuit leads to emergency situations [1,2]. The electrical equipment of the ring network spare line is exposed to high emergency short-circuit currents, and the consumers powered by the spare transformer are turned off. It is possible to minimize and eliminate the damages caused by the above mentioned cases by inhibiting the switching on of the circuitbreaker of the automatic transfer switch.


2018 ◽  
Vol 18 (4) ◽  
pp. 162-167 ◽  
Author(s):  
Miroslav Gutten ◽  
Daniel Korenciak ◽  
Matej Kucera ◽  
Richard Janura ◽  
Adam Glowacz ◽  
...  

Abstract The authors describe experimental and theoretical analyses of faults of power transformer winding. Faults were caused by mechanical effect of short-circuit currents. Measurements of transformer were carried out in high-voltage laboratory. Frequency and time diagnostic methods (method SFRA - Sweep Frequency Response Analysis, impact test) were used for the analyses. Coils of transformer windings were diagnosed by means of the SFRA method and the time impact test. The analyzed methods had a significant sensitivity to a relatively small deformation of coil. In the analysis a new technique for analyzing the effects of short-circuit currents is introduced. This technique is developed for high-voltage transformers (different types of power). The proposed analyses show that it is necessary to analyze the value of short-circuit current. Short-circuit current represents a danger for the operation of the power transformer. The proposed approach can be used for other types of transformers. Moreover, the presented techniques have a potential application for fault diagnosis of electrical equipment such as: transformers and electrical machines.


2008 ◽  
Vol 3 (4) ◽  
pp. 68-73
Author(s):  
Aleksandr V. Akimov ◽  
Petr A. Bak ◽  
Andrey A. Korepanov ◽  
Pavel V. Logachev ◽  
Viktor D. Bochkov ◽  
...  

The circuit of modulator, serving to supply inductive-resistive load in double-pulse mode with currents up to 10 kA and pulse duration of 300 ns, is described. As switching components unheated cathode thyratrons (pseudospark switches) TPI1-10k/50 and TPI5-10k/50 with anode voltage up to 50 kV have been used. The results of tests, confirming possibility of the thyratron reverse dielectric strength recovery within some microseconds after switching of 10 kA forward anode current, are presented.


2021 ◽  
pp. 98-100
Author(s):  
I. Radko ◽  
◽  
V. Nalivayko ◽  
O. Okushko ◽  
I. Bolbot ◽  
...  

According to PUE-2017, each group line must be protected against short circuits. Instant disconnection (cut-off) of the line in the event of short circuits provides an electromagnetic release of the circuit breaker. Reliable tripping is possible if the current of a single-phase short circuit is greater than the instantaneous tripping current. Today on the market are widely available circuit breakers with characteristics "B", "C" and "D", which are characterized by different multiplicities of the cut-off current of the electromagnetic release. Some European companies produce circuit breakers with other characteristics, which greatly expands the possibilities protection of electrical equipment. The difficulty in organizing the selectivity of protection is that the circuit breakers of modular design when switching off short circuits are characterized by the same switching time (not more than 0.05 s). The purpose of the research is to find ways to organize the selectivity of protection in electrical networks with voltage up to 1000 V using reliable values of short-circuit currents. In networks with a voltage of up to 1000 V, the current of a single-phase short circuit can be calculated fairly accurately if the exact values of all sections of the electrical network are known. In practice, it is not always possible to obtain reliable data on the numerical characteristics of the 0.4 kV network to which a new energy facility is connected. Therefore, it is proposed to consider part of the network as an active quadrupole, the characteristics of which are obtained by measurements at the point of connection. For further calculations it is necessary to know the voltage at the clamps of the four-pole scheme and the internal impedance. Based on the theory of four-pole scheme, you can get the original data for calculations without calculating the internal parameters of four-poles scheme. Thus, it is proposed to use a hybrid method for estimating the magnitude of probable short-circuit currents in electrical networks up to 1000 V when designing new energy facilities. Credible values of short-circuit currents will allow to organize selective protection of electric networks.