scholarly journals An Artificial Neural Network Developed in MATLAB-Simulink for Reconstruction a Distorted Secondary Current Waveform. Part 1

Author(s):  
Yu. V. Rumiantsev ◽  
F. A. Romaniuk

Recently, there has been an increased interest in the use of artificial neural networks in various branches of the electric power industry including relay protection. Аrtificial neural networks are one of the fastest growing areas in artificial intelligence technology. Recently, there has been an increased interest in the use of аrtificial neural networks in the electric power engineering, including relay protection. Existing microprocessor-based relay protection devices use a traditional digital signal processing of the monitored signals which is reduced to a multiplying the values of successive samples of the monitored current and voltage signals by predetermined coefficients in order to calculate their RMS values. In this case, the calculated RMS values often do not reflect the real processes occurring in the protected electrical equipment due to, for example, current transformer saturation because of the DC component presence in the fault current. When the current transformer is saturated, its secondary current waveform has a characteristic non-periodic distorted form, which is significantly differs from its primary (true) waveform, which causes underestimation of the calculated RMS value of the secondary current compared to its true value. In its turn, this causes to a trip time delay or even to a relay protection devices operation failure. The use of аrtificial neural networks in conjunction with a traditional digital signal processing provides a different approach to the functioning of both the measuring and logical parts of the microprocessor-based relay protection devices, which significantly increases the speed and reliability of such relay protection devices in comparison with their traditional implementation. A possible application of the аrtificial neural networks for the relay protection purposes is the fault occurrence detection and its type identification, current transformer secondary current waveform distortion restoration due to its saturation up to its true value, detection the distorted and undistorted sections of the current transformer secondary current waveform during its saturation, primary power equipment abnormal operating modes detection, for example, power transformer magnetizing current inrush. The article describes in detail the stages of the practical implementation of the аrtificial neural networks in the MATLAB-Simulink environment by the example of its use to restore the distorted current transformer secondary current waveform due to saturation.

2014 ◽  
Vol 668-669 ◽  
pp. 857-861
Author(s):  
Peng Fei Hu ◽  
Yu Xiang Yuan ◽  
Zhi Juan Qu ◽  
Xue Ping Jiang

To improve the reliability and integration of relay protection devices in power, the system on chip design for multi-principle of relay protection on FPGA is proposed. The data acquisition, digital signal processing, hardware protection algorithm, FPGA and MCU process scheduling, MCU and peripheral devices communication are designed, the hardware compilation model is set up by QuartusII on FPGA, and the simulation and experimental verification are performed. The results show that the proposed system can improve the speed of hardware protection and reduce the volume of the device, and has reconstruction on architecture.


2020 ◽  
Vol 22 (1-2) ◽  
pp. 112-118
Author(s):  
Nenad Belčević ◽  
◽  
Zoran Stojanović

The main function of current transformers is to adapt the high values of the primary current to values suitable for the operation of relay protection devices, i.e. measuring devices. Under normal conditions, a current transformer transforms the current in a virtually permanent ratio, and practically without a phase shift, so the secondary current is actually a scaled value of the primary current. However, when a fault occurs in the power system, currents reach high values. As a result, the flux in the core of the current transformer can reach values above the knee of the magnetization characteristic, causing saturation of the current transformer. When saturation occurs, the secondary current is no longer a scaled value of the primary current, but is deformed. Deformation of the secondary current may cause malfunctioning of some relay protection devices. The development of digital relay protection has made it possible to perform software saturation compensation by applying certain algorithms, thus eliminating the negative consequences that saturation of the current transformer causes. In this paper, one of the possible approaches for compensation of saturation is analyzed, which is based on the application of an equivalent scheme and magnetization curve of the current transformer. Two typical approaches have been singled out, which have been analyzed and tested in more detail. Testing was performed in the MATLAB/Simulink.